ISBN 978-0-626-40354-6 SANS 10400-XA:2021
Edition 2
SOUTH AFRICAN NATIONAL STANDARD
The application of the National Building Regulations Part X: Environmental sustainability Part XA: Energy usage in buildings
Published by the South African Bureau of Standards 1 Dr Lategan Road Groenkloof Private Bag X191 Pretoria 0001 Tel: +27 12 428 7911 Fax: +27 12 344 1568 www.sabs.co.za SABS
This page has been left blank intentionally
COPYRIGHT PROTECTED DOCUMENT
© SABS
In terms of the Standards Act 8 of 2008, the copyright in all South African National Standards or any other publications published by the SABS Standards Division, vests in the SABS. Any use of South African National Standards is limited to use specifically prescribed by the SABS. In the case of a South African National Standard based on an international standard, ownership of the copyright vests in the organization from which the SABS adopted the standard, whether it be under licence or membership agreement. The SABS is obliged to protect such copyright and is authorized to make the relevant international organization aware of any misuse thereof. Unless exemption has been granted, no extract or full text of any South African National Standard may be copied, reproduced, stored in a retrieval system or transmitted in any form or by any means without prior written permission from the SABS Standards Division. This does not preclude the free use, in the course of implementing the standard, of necessary details such as symbols, and size, type or grade designations. If these details are to be used for any purpose other than implementation, prior written permission must be obtained.
Details, advice and limitations of use can be obtained from the Manager: Standards Sales and Information Services. Tel: +27 (0) 12 428 6883 email: sales@sabs.co.za
SABS – Standards Division
The objective of the SABS Standards Division is to develop, promote and maintain South African National Standards. This objective is incorporated in the Standards Act, 2008 (Act No. 8 of 2008).
The SABS continuously strives to improve the quality of its products and services and would therefore be grateful if anyone finding an inaccuracy or ambiguity while using this standard would inform the secretary of the technical committee responsible, the identity of which can be found in the foreword.
Buying Standards
Contact the Sales Office for South African and international standards, which are available in both electronic and hard copy format. Tel: +27 (0) 12 428 6883 email: sales@sabs.co.za
South African National Standards are also available online from the SABS Webstore www.store.sabs.co.za
Information on Standards
SABS Customer Services provide comprehensive standards-related information on national, regional and international standards. Tel: +27 (0) 12 428 7911 / 0861 27 7227 email: info@sabs.co.za
SANS 10400-XA:2021 Edition 2
| Change No. | Date | Scope |
|---|---|---|
Foreword
This South African standard was prepared by National Committee SABS/TC 060, Standards which address the National Building Regulations (NBRS), in accordance with procedures of the South African Bureau of Standards, in compliance with annex 3 of the WTO/TBT agreement.
This document was approved for publication in November 2021.
This document supersedes SANS 10400-XA:2011 (edition 1).
Compliance with the requirements of this document will be deemed to be compliance with the requirements of part XA of the National Building Regulations, issued in terms of the National Building Regulations and Building Standards Act, 1977 (Act No. 103 of 1977).
Compliance with this document cannot confer immunity from legal obligations.
SANS 10400 consists of the following parts, under the general title The application of the National Building Regulations :
Part A: General principles and requirements
Part B: Structural design.
Part C: Dimensions.
Part D: Public safety.
Part F: Site operations.
Part G: Excavations.
Part H: Foundations.
Part J: Floors.
Part K: Walls.
Part L: Roofs.
Part M: Stairways.
Part N: Glazing.
Part O: Lighting and ventilation.
Part P: Drainage.
© SABS
SANS 10400-XA:2021
Edition 2
Foreword (concluded)
Part Q: Non-water-borne means of sanitary disposal.
Part R: Stormwater disposal.
Part S: Facilities for persons with disabilities.
Part T: Fire protection.
Part V: Space heating.
Part W: Fire installation.
Part X: Environmental sustainability.
Part XA: Energy usage in buildings.
Annex B forms an integral part of this document. Annexes A, C, D, E and F are for information only.
This document should be read in conjunction with SANS 10400-A.
© SABS 1
SANS 10400-XA:2021 Edition 2
Contents
Foreword
NATIONAL BUILDING REGULATIONS
Page
1 Scope ........................................................................................................................................................ 5
2 Normative references .............................................................................................................................. 5
3 Terms and definitions .............................................................................................................................. 7
4 Requirements ......................................................................................................................................... 10
5 Building envelope .................................................................................................................................. 17
5.1 Orientation ................................................................................................................................... 17 5.2 Shading ........................................................................................................................................ 18 5.3 Fenestration ................................................................................................................................. 20 5.4 Floors ............................................................................................................................................ 24 5.5 External walls .............................................................................................................................. 24 5.6 Roof assembly ............................................................................................................................. 26 5.7 Building sealing ........................................................................................................................... 29
6 Services .................................................................................................................................................. 30
6.1 Hot water supply ......................................................................................................................... 30 6.2 Lighting ......................................................................................................................................... 33 6.3 Air conditioning ............................................................................................................................ 34
Annex A (informative) South African Energy Trajectory ..................................................................... 36
Annex B (normative) Modelling conditions ......................................................................................... 37
Annex C (informative) List of cities and towns by energy zones ....................................................... 41
Annex D (informative) Types of shading devices ................................................................................ 59
Annex E (informative) Whole glazing element performances values ............................................... 60
Annex F (informative) The installation of insulation in roof assemblies ............................................ 61
Bibliography .................................................................................................................................. 64
2 © SABS
SANS 10400-XA:2021
Edition 2
NATIONAL BUILDING REGULATIONS
PART X — ENVIRONMENTAL SUSTAINABILITY
XA ENERGY USAGE IN BUILDINGS
XA1: In order to contribute to the reduction of greenhouse gases buildings, and extensions to buildings in respect of which plans and specifications are to be drawn and submitted in terms of the Act, having A1, A2, A3, A4, C1, C2, E1, E2, E3, E4, F1, F2, F3, G1, H1, H2, H3, H4 and H5 occupancies or building classifications in accordance with regulation A20, excluding garage and storage areas contained within such occupancies, shall be designed and constructed so that they
a) are capable of using energy efficiently while fulfilling user needs in relation to vertical transport, if any, thermal comfort, lighting and hot water; or
b) have a building envelope and services which facilitate the efficient use of energy appropriate to their function and use, internal environment and geographical location.
Equipment and plant required for conducting the business of the occupant shall be excluded from these requirements.
XA2: At least 50 % (volume fraction) of the annual average hot water heating requirement shall be provided by means other than electrical resistance heating including but not limited to solar heating, heat pumps, heat recovery from other systems or processes and renewable combustible fuel.
XA3: The requirements of sub-regulation XA1 shall be deemed to be satisfied when such building is designed and constructed in accordance with the following requirements:
a) has an orientation, shading, services and building envelope in accordance with this part of SANS 10400; or
b) is the subject of a rational design by a competent person, which demonstrates that the energy usage of such building is equivalent to or better than that which would have been achieved by compliance with the requirements of this part of SANS 10400,
c) has a theoretical energy usage performance, determined using certified thermal calculation software, less than or equal to that of a reference building in accordance with SANS 10400-Part XA.
© SABS 3
SANS 10400-XA:2021 Edition 2
This page is intentionally left blank
4 © SABS
SANS 10400-XA:2021
Edition 2
The application of the National Building Regulations Part X: Environmental sustainability Part XA: Energy usage in buildings 1 Scope
This part of SANS 10400 provides deemed-to-satisfy requirements for compliance with part XA (Energy usage in buildings) of the National Building Regulations.
NOTE The prescribed energy efficiency performance levels according to the South African Energy Trajectory of The National Energy Efficiency Strategy as published by the Department of Energy are given in annex A.
2 Normative references
The following referenced documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. Information on currently valid national and international standards can be obtained from the South African Bureau of Standards.
ANSI/NFRC 100, Procedure for determining fenestration product U-factors.
ANSI/NFRC 200, Procedure for determining fenestration product solar heat gain coefficient and visible transmittance at normal incidence.
SANS 151, Fixed electric storage water heaters.
SANS 613, Fenestration products – Mechanical performance criteria.
SANS 1307, Domestic storage solar water heating systems.
SANS 1352, The installation, maintenance, replacement and repair of domestic air source water heating heat pump systems.
SANS 1539, Appliances operating on liquefied petroleum gas (LPG) or natural gas (NG) – Safety aspects.
SANS 1687, Domestic air source water heating heat pump systems.
SANS 1808-24 , Water supply and distribution system components – Part 24: Gas-operated water heaters.
SANS 5151, Non-ducted air conditioners and heat pumps – Testing and rating for performance.
SANS 8301/ISO 8301, Thermal insulation – Determination of steady-state thermal resistance and related properties – Heat flow meter apparatus .
© SABS 5
SANS 10400-XA:2021 Edition 2
SANS 10087-1, The handling, storage, distribution and maintenance of liquefied petroleum gas in domestic, commercial, and industrial installations – Liquefied petroleum gas installations involving gas storage containers of individual water capacity not exceeding 500 L and a combined water capacity not exceeding 3 000 L per installation.
SANS 10106, The installation, maintenance, repair and replacement of domestic solar water heating systems.
SANS 10252-1, Water supply and drainage for buildings – Part 1: Water supply installations for buildings.
SANS 10254, The installation, maintenance, replacement and repair of fixed electric storage water heating systems.
SANS 10400-O, The application of the National Building Regulations – Part O – Lighting and ventilation.
SANS 13253/ISO 13253, Ducted air-conditioners and air-to-air heat pumps – Testing and rating for performance.
SANS 54511-2/EN 14511-2, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling – Part 2: Test conditions.
SANS 54511-3/EN 14511-3, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling – Part 3: Test methods.
6 © SABS
SANS 10400-XA:2021
Edition 2
3 Terms and definitions
For the purposes of this document, the definitions given in Regulation AZ2 of The National Building Regulations (some of which are repeated for convenience) and the following apply.
3.1 building envelope elements of a building that separate the outside environment from internal spaces where these internal spaces are required to have a controlled internal environment for thermal comfort
NOTE It excludes internal spaces such as garages, storerooms, and enclosed verandas only where these areas have suitably performing separating walls, floors roofs and ceilings and their components such as windows, doors and roof lights meet external performance requirements for energy efficiency
3.2 category 1 building building which
a) is designated as being of class A3, A4, F2, G1, H2, H3, or H4 occupancy in terms of Regulation A20
b) has no basements,
c) has a maximum length of 6,0 m between intersecting walls or members providing lateral support, and
d) has a floor area that does not exceed 80 m [2]
3.3 certified thermal calculation software software that is certified by the Board of Agrément South Africa, in terms of Agrément South Africa’s Energy Software Protocols, as being fit for thermal modelling or calculation purposes in terms of the National Building Regulations
NOTE Board of Agrément South Africa is the body that operates under the delegation of authority of the Minister of Public Works.
3.4 competent person person who is qualified by their education, training, experience, and contextual knowledge to make a determination regarding the performance of a building or part thereof in relation to a functional regulation or to undertake such duties as may be assigned to them in terms of the National Building Regulations
3.5 CR-value time constant (hours) of a composite element, such as a wall, and being the arithmetical product of total C-value and the total R-value
3.6 deemed-to-satisfy requirement non-mandatory requirement, the compliance with which ensures compliance with a functional regulation
© SABS 7
SANS 10400-XA:2021 Edition 2
3.7 door glazed or un-glazed, framed, or frameless hinged, pivoting, revolving, roll-up, retracting, sliding, stacking or tilting barrier at the entrance, exit, side of a building or fire escape forming part of a building envelope
3.8 energy efficiency ratio EER ratio of output heating energy to input electrical energy of a water heating device
3.9 electrical resistance heating electric current derived from the national electrical supply grid passed through a conductor to produce heat
3.10 equipment control devices and components of systems other than appliances which are not permanently installed and integrated for the express purpose of providing control of environmental conditions for the building
3.11 fenestration glazed opening in a building envelope, including windows, doors, and roof lights
3.12 fenestration area area that includes glazing and framing elements that are fixed or movable, opaque, translucent, or transparent
3.13 functional regulation regulation that sets out in qualitative terms what is required of a building or building element or building component in respect of a characteristic, without specifying the method of construction, dimensions, or materials to be used
3.14 nett floor area floor area within the building envelope, including the area occupied by vertical elements such as internal walls as well as lift wells, enclosed stairs, and storage areas and rooms
3.15 orientation direction that a building envelope element faces, i.e. the direction of a vector perpendicular to and pointing away from the surface outside of the element
3.16 reference building hypothetical building that has the same building envelope dimensions, internal layout, functionality, external arrangements and orientation as the proposed building with the deemed-to-satisfy provisions applied and is used to determine the maximum allowable energy usage per annum and average demand for the proposed building
8 © SABS
SANS 10400-XA:2021
Edition 2
3.17 roof assembly building cover and its supporting structure, including any ceiling attached to such structure and any additional components such as insulation
3.18 roof covering covering of the upper exterior surface of a building or shelter which provides protection against weather, notably rain or snow, and heat, wind and sunlight
3.19 roof light opaque, translucent, or transparent element in a roof which is within 0 °and 70 ° of the horizontal plane
3.20 R-value thermal resistance (m².K/W) of a component
NOTE This is the inverse of the time rate of heat flow through a body from one of its bounding surfaces to the other surface for a unit temperature difference between the two surfaces, under steady state conditions, per unit area.
3.21 shading minimizing or excluding solar energy from reaching fenestration
3.22 solar heat gain coefficient SHGC unitless quantity depicting the ratio of the solar heat gain entering the space through the fenestration area to the incident solar radiation
3.23 spacer system series of brackets and sub-purlins, or a halter for standing seam profile, that provide
a) a cavity between the underside of the cladding and top of purlins to accommodate the required thickness of flexible bulk insulation without compression,
b) a platform for the mechanical anchoring of the cladding to the supporting structure,
c) transfer of imposed loads on the cladding to the supporting structure without excessive deformation whilst retaining stability, and
d) minimal thermal bridging
3.24 surface density area density (also known as a real density, superficial density, areic density, mass thickness, column density, or density thickness) of a two-dimensional object calculated as the mass per unit area
NOTE For a walling system, the area density is the total mass per square meter of a walling system.
© SABS 9
SANS 10400-XA:2021 Edition 2
3.25 total R-value sum of the R-values of the individual component layers in a composite element, including the air space and associated surface thermal resistances, measured in m².K/W. R-values
NOTE The R-values of the individual component layers are in accordance with the constants and generic conductance values of SANS 694 or the results when tested to SANS 8301.
3.26 total U-value thermal transmittance (W/m²K) of the composite element, including the air space and associated surface emittance
3.27 whole glazing element glazing and frame as a unit
4 Requirements
4.1 The functional regulation XA1 contained in part XA of the National Building shall be deemed to be satisfied where the building can use energy efficiently while fulfilling user needs in relation to
a) the vertical transport, if any,
b) thermal comfort,
c) lighting and
d) hot water
by any one of the means given in 4.2, 4.3 or 4.4.
4.2 In any building of occupancy classified in terms of Regulation A20 as A1, A2, A3, A4, E2, E3, F1, F2, F3, G1, H1, H2, H3, H4 and H5, a competent person that satisfies the requirements of Regulation A19 of The National Building Regulations, certifies that such building (excluding garage, storage, and other defined areas) has a theoretical annual energy consumption and demand less than or equal to the values specified in table 1 and table 2.
NOTE 1 Modelling conditions are provided in annex B.
NOTE 2 Only those occupancies for which data are available are listed in tables 1 and 2.
4.3 In any building of occupancy classified in terms of Regulation A20 as A1, A2, A3, A4, C1, C2, E1, E2, E3, E4, F1, F2, F3, G1, H1, H2, H3, H4, and H5, a competent person that satisfies the requirements of Regulation A19 of The National Building Regulations, demonstrates, by using certified thermal calculation software, that the building (excluding garage, storage areas and other defined areas) under consideration has a theoretical energy usage and demand less than or equal to a reference building that complies with the requirements of 4.4.
NOTE Modelling conditions are provided in annex B.
4.4 In any new building or portion of addition or alteration (or both) to an existing building (excluding garage, storage, and other defined areas) of occupancy classified in terms of Regulation A20 as A1, A2, A3, A4, C1, C2, E1, E2, E3, E4, F1, F2, F3, G1, H1, H2, H3, H4, and H5,
a) the orientation is in accordance with the requirements of 5.1,
b) the shading is in accordance with the requirements of 5.2,
10 © SABS
SANS 10400-XA:2021
Edition 2
c) fenestration is in accordance with the requirements of 5.3,
d) floors are in accordance with the requirements of 5.4,
e) external walls are in accordance with the requirements of 5.5,
f) roof and ceiling assemblies are in accordance with the requirements of 5.6,
g) the building sealing is in accordance with the requirements of 5.7, and
h) services that use energy or control the use of energy, excluding equipment and plant required for conducting the business of the occupant, but including fixed space cooling, fixed space heating and all fixed lighting, are required to provide energy efficiency levels in accordance with the requirements of clause 6.
NOTE 1 Energy zones are in accordance with figure 1.
NOTE 2 Cities and towns listed alphabetically by Energy zones are listed in annex C.
© SABS 11
SANS 10400-XA:2021 Edition 2
NOTE Energy zone map Available from: https://csir.maps.arcgis.com/apps/webappviewer/index.html?id=79602766e2b54ede82625c939ac1814b)
Figure 1 — Energy zone map
12 © SABS
SANS 10400-XA:2021
Edition 2
Table 1 — Maximum annual energy consumption per building classification for each energy zone (kWh/m²/a) (Energy zones as shown in figure 1 and annex C)
| 1 | 2 | Col3 | Col4 | Col5 | Col6 | Col7 | Col8 | Col9 |
|---|---|---|---|---|---|---|---|---|
| Class of occupancy | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones |
| Class of occupancy | **1 ** | **2 ** | **3 ** | **4 ** | **5 ** | 5H | **6 ** | **7 ** |
| A1 Entertainment and public assembly Occupancy where persons gather to eat, drink, dance or participate in other recreation. |
75 | 75 | 95 | 70 | 95 | 95 | 80 | 80 |
| A2 Theatrical and indoor sport Occupancy where persons gather for the viewing of theatrical, operatic, orchestral, choral, cinematographical or sport performances. |
95 | 95 | 110 | 90 | 110 | 110 | 105 | 105 |
| A3 Places of instruction Occupancy other than primary or secondary schools, where students or other persons assemble for the purpose of tuition or learning. |
110 | 155 | 110 | 125 | 140 | 140 | 120 | 120 |
| A3 Places of instruction Occupancy where school children assemble for the purpose of tuition or learning |
60 | 65 | 55 | 60 | 55 | 60 | 65 | 65 |
| A4 Worship Occupancy where persons assemble for the purpose of worshipping. |
70 | 45 | 45 | 40 | 50 | 40 | 70 | 70 |
| E2 Hospital Occupancy where people are cared for or treated because of physical or mental disabilities and where they are generally bed-ridden. |
325 | 335 | 225 | 295 | 295 | 230 | 345 | 345 |
| E3 Other institutional (residential) Occupancy where groups of people who either are not fully fit, or who are restricted in their movements or their ability to make decisions, reside and are cared for |
120 | 95 | 90 | 90 | 100 | 80 | 130 | 130 |
| F1 Large shop Occupancy where merchandise is displayed and offered for sale to the public and the floor area exceeds 250 m². |
125 | 200 | 155 | 180 | 185 | 150 | 125 | 125 |
| F2 Small shop Occupancy where merchandise is displayed and offered for sale to the public and the floor area does not exceed 250 m². |
75 | 150 | 100 | 125 | 130 | 95 | 80 | 80 |
© SABS 13
SANS 10400-XA:2021 Edition 2
| Table 1 (concluded) | Col2 | Col3 | Col4 | Col5 | Col6 | Col7 | Col8 | Col9 |
|---|---|---|---|---|---|---|---|---|
| 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
| Class of occupancy | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones |
| Class of occupancy | **1 ** | **2 ** | **3 ** | **4 ** | **5 ** | 5H | **6 ** | **7 ** |
| F3 Wholesaler's store Occupancy where goods are displayed and stored and where only a limited selected group of persons is present at any one time**. ** |
125 | 200 | 155 | 180 | 185 | 150 | 125 | 125 |
| G1 Offices Large multi-storey office buildings, banks, consulting rooms and similar uses with lifts and energy consuming services that operate on a typical daytime occupancy. |
90 | 105 | 110 | 95 | 110 | 95 | 100 | 100 |
| G1 Offices Stand-alone blocks and / or campus of buildings that form an office park but operate separately |
70 | 150 | 190 | 145 | 180 | 165 | 75 | 75 |
| H1 Hotel Occupancy where persons rent furnished rooms, not being dwelling units. |
125 | 130 | 100 | 115 | 125 | 95 | 140 | 140 |
| H2 Dormitory Occupancy where groups of people are accommodated in one room |
155 | 170 | 160 | 175 | 160 | 160 | 160 | 180 |
| H3 Domestic residence Occupancy consisting of two or more dwelling units on a single site. |
90 | 100 | 50 | 80 | 85 | 60 | 110 | 110 |
| H4 Dwelling house Occupancy consisting of a dwelling unit on its own site, including a garage and other domestic outbuilding, if any. |
95 | 100 | 50 | 80 | 85 | 60 | 110 | 110 |
| H5 Hospitality Occupancy where unrelated persons rent furnished rooms on a transient basis within a dwelling house or domestic residence with sleeping accommodation for not more than 16 persons within a dwelling unit |
120 | 130 | 110 | 120 | 115 | 135 | 135 | 135 |
14 © SABS
SANS 10400-XA:2021
Edition 2
| Table 2 — Maximum Annual dem each energy zone (VA/m2) (see Ene | mand intensity per building classification for ergy zones as shown in figure 1 and annex C) | Col3 | Col4 | Col5 | Col6 | Col7 | Col8 | Col9 |
|---|---|---|---|---|---|---|---|---|
| 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
| Class of occupancy | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones |
| Class of occupancy | **1 ** | **2 ** | **3 ** | **4 ** | **5 ** | 5H | **6 ** | **7 ** |
| A1 Entertainment and public assembly Occupancy where persons gather to eat, drink, dance or participate in other recreation |
30 | 30 | 38 | 28 | 38 | 38 | 32 | 32 |
| A2 Theatrical and indoor sport Occupancy where persons gather for the viewing of theatrical, operatic, orchestral, choral, cinematographical or sport performances |
38 | 38 | 44 | 36 | 44 | 44 | 42 | 42 |
| A3 Places of instruction Occupancy other than primary or secondary schools, where students or other persons assemble for the purpose of tuition or learning. |
44 | 62 | 44 | 50 | 56 | 56 | 48 | 48 |
| A3 Places of instruction Occupancy where school children assemble for the purpose of tuition or learning |
24 | 26 | 22 | 24 | 22 | 24 | 24 | 24 |
| A4 Worship Occupancy where persons assemble for the purpose of worshipping |
28 | 18 | 18 | 16 | 20 | 16 | 28 | 28 |
| E2 Hospital Occupancy where people are cared for or treated because of physical or mental disabilities and where they are generally bed-ridden. |
130 | 134 | 90 | 118 | 118 | 92 | 138 | 138 |
| E3 Other institutional (residential) Occupancy where groups of people who either are not fully fit, or who are restricted in their movements or their ability to make decisions, reside and are cared for |
48 | 38 | 36 | 36 | 40 | 32 | 52 | 52 |
| F1 Large shop Occupancy where merchandise is displayed and offered for sale to the public and the floor area exceeds 250 m² |
50 | 80 | 62 | 72 | 74 | 60 | 50 | 50 |
| F2 Small shop Occupancy where merchandise is displayed and offered for sale to the public and the floor area does not exceed 250 m² |
30 | 60 | 40 | 50 | 52 | 38 | 32 | 32 |
| F3 Wholesaler's store Occupancy where goods are displayed and stored and where only a limited selected group of persons is present at any one time |
50 | 80 | 62 | 72 | 74 | 60 | 50 | 50 |
© SABS 15
SANS 10400-XA:2021 Edition 2
| Table 2 (concluded) | Col2 | Col3 | Col4 | Col5 | Col6 | Col7 | Col8 | Col9 |
|---|---|---|---|---|---|---|---|---|
| 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
| Class of occupancy | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones | Energy zones |
| Class of occupancy | **1 ** | **2 ** | **3 ** | **4 ** | **5 ** | 5H | **6 ** | **7 ** |
| G1 Offices Large multi-storey office buildings, banks, consulting rooms and similar uses with lifts and energy consuming services that operate on a typical daytime occupancy. |
36 | 42 | 44 | 38 | 44 |
38 | 40 | 40 |
| G1 Offices Stand-alone blocks or campus (or both) of buildings that form an office park but operate separately |
28 | 60 | 76 | 58 | 72 | 66 | 30 | 30 |
| H1 Hotel Occupancy where persons rent furnished rooms, not being dwelling units |
80 | 60 | 46 | 54 | 54 | 44 | 80 | 80 |
| H2 Dormitory Occupancy where groups of people are accommodated in one room |
80 | 74 | 94 | 78 | 90 | 90 | 80 | 80 |
| H3 Domestic residence Occupancy consisting of two or more dwelling units on a single site. |
58 | 66 | 40 | 56 | 56 | 46 | 60 | 60 |
| H4 Dwelling house Occupancy consisting of a dwelling unit on its own site, including a garage and other domestic outbuilding, if any |
58 | 66 | 40 | 56 | 56 |
46 | 60 | 60 |
| H5 Hospitality Occupancy where unrelated persons rent furnished rooms on a transient basis within a dwelling house or domestic residence with sleeping accommodation for not more than 16 persons within a dwelling unit |
58 | 58 | 62 | 56 | 60 |
60 | 60 | 60 |
16 © SABS
SANS 10400-XA:2021
Edition 2
5 Building envelope
5.1 Orientation
Orientation shall be defined as one of either North, North-East, East, South East, South, South–West, West or North-West as shown in figure 2, and refers to the façade that contains the largest combined area of fenestration elements for solar heat gain in Energy zones 1, 2, 3, 4, 5, 6 and 7 or the façade with the largest openings for ventilation in Energy zone 5H.
NOTE 1 For energy zones see figure 1.
NOTE 2 Buildings should be orientated to face North East, North or North-West as shown figure 2 to facilitate winter solar gain, except for in Zone 5H.
NOTE 3 In Zone 5H buildings should be orientated to make use of the prevailing winds (see figure 3) to cool the building through natural ventilation.
Figure 2 — Orientation sectors
© SABS 17
SANS 10400-XA:2021 Edition 2
NOTE Adapted from the National Laboratory of Sustainable Energy.
Figure 3 — Prevailing winds of South Africa
5.2 Shading
NOTE Shading against summer solar radiation can be provided by
a) shading devices,
b) glass tinting and coating,
c) fenestration types and design, or
d) size of area of glazing per elevation.
5.2.1 Where shading is implemented to satisfy fenestration requirements, the building shall
a) have a permanent feature such as a veranda, balcony, fixed canopy, eaves, or shading hood with opaque property, which
-
extends horizontally on both sides of the glazing for the same projection distance, P in figure 4 for elevations with West, North-West, North, North-East and East Sector orientation, and
-
provides the equivalent shading with a reveal or other method.
b) alternatively have an external shading device, such as a shutter, blind, building screen with vertical or horizontal blades, battens or slats, which
-
can restrict at least 80 % by area of astronomical summer solar radiation, and
-
if adjustable, is readily operated either manually, mechanically, or electronically by the building occupants.
18 © SABS
SANS 10400-XA:2021
Edition 2
NOTE 1 Designers should make provision to ensure that there is not excessive shading of desirable winter solar gains.
NOTE 2 Astronomical summer refers to the period from spring equinox though to autumnal equinox (in the southern hemisphere the period 23 September until 21 March).
5.2.2 The projection of the shading device (P) shall not be less than the height (H) multiplied by the factor given in table 3 for the appropriate latitude for the site.
NOTE 1 Exceeding dimension P will prevent beneficial winter sun from striking the fenestration. Examples of shading are given in annex D.
NOTE 2 Screens attached to the exterior of the building can act as a chimney in case of a fire and measures to avoid such a situation arising should be taken note of.
NOTE 3 Fixed vertical shading devices should not compromise the requirements for natural lighting in accordance with SANS 10400-O.
Table 3 — Multiplier for shading projection on facades with West, North-West, North, North-East and East sector orientation
| 1 | 2 |
|---|---|
| Latitude (º South) |
Multiplier |
| ≤ 22º | 0,33 |
| ≤ 24º | 0,36 |
| ≤ 26º | 0,40 |
| ≤ 28º | 0,42 |
| ≤ 30º | 0,46 |
| ≤ 32º | 0,50 |
| >32º | 0,54 |
| NOTE A list of towns with their latitudes are provided in table C.1, |
NOTE A list of towns with their latitudes are provided in table C.1, |
© SABS 19
SANS 10400-XA:2021 Edition 2
Figure 4 — Explanation of the shading device/feature
5.3 Fenestration
5.3.1 Fenestration includes fenestration applied to external walls and roofs forming part of the building envelope.
NOTE 1 Glazing elements require total U-values and SHGCs and are assessed for the combined effect of glass and frames. The measurements of these total U-values and SHGCs are specified in the guidelines of the National Fenestration Rating Council (ANSI/NFRC) and the indicative ranges of these performance values are given in annex E.
NOTE 2 Any centre of glass values (for both U and SHGC values) of any fenestration product that has not been calculated in a whole glazed system should not be used.
5.3.2 Total U-values provided or calculated (or both) shall be determined in accordance with ANSI/NFRC 100.
20 © SABS
SANS 10400-XA:2021
Edition 2
5.3.3 The Solar Heat Gain Coefficient (SHGC) provided or calculated (or both) shall be determined in accordance with ANSI/NFRC 200.
5.3.4 The weighted average (by fenestration area) per storey of vertical fenestration with West, North-West, North, North-East and East sector orientation (see figure 2) shall have performance values certified by the glazier or a competent person to be equal or less than the relevant value given in table 4.
5.3.5 The weighted average (by fenestration area) per storey of vertical fenestration with South-West, South, and South-Eastern orientation (see figure 2) shall have performance values certified by the glazier or a competent person to be equal or less than the relevant value given in table 4.
NOTE 1 Values calculated in 5.3.4 and 5.3.5 are independent of each other and therefore will in no way affect each other. Should one exceed the performance requirement the performance cannot be compromised in the second. The requirements of each clause are to be satisfied independent of the other.
NOTE 2 These values are strictly applicable to the storey considered. Should the performance of one storey exceed requirements this cannot be traded off in a second storey.
Table 4 — Area weighted average maximum whole fenestration element performance values for vertical fenestration
| 1 | 2 | 3 | Col4 | Col5 |
|---|---|---|---|---|
| Total fenestration area for each storey/nett floor area for each storey (%) |
U-Value (W/m².K) |
Maximum solar heat gain coefficient (SHGC) | Maximum solar heat gain coefficient (SHGC) | Maximum solar heat gain coefficient (SHGC) |
| Total fenestration area for each storey/nett floor area for each storey (%) |
U-Value (W/m².K) |
Vertical fenestration with West, North- West, North, North-East and East sector orientation (see figure 2) |
Vertical fenestration with West, North- West, North, North-East and East sector orientation (see figure 2) |
Vertical fenestration with South-West, South and South-Eastern orientation (see figure 2) |
| Total fenestration area for each storey/nett floor area for each storey (%) |
U-Value (W/m².K) |
With shading in accordance with 5.2.2 |
With no shading or not in accordance with 5.2.2 |
All |
| ≤ 20 % | Any solution | Any solution | Any solution | Any solution |
| ≤ 25 % | 5,20 | 0,66 | 0,49 | Any solution |
| ≤ 30 % | 4,40 | 0,53 | 0,44 | Any solution |
| ≤ 35 % | 3,80 | 0,49 | 0,40 | Any solution |
| ≤ 40 % | 3,30 | 0,44 | 0,35 | Any solution |
| ≤ 45 % | 3,00 | 0,40 | 0,33 | Any solution |
| ≤ 50 % | 2,60 | 0,35 | 0,30 | Any solution |
| ≤ 55 % | 2,40 | 0,33 | 0,28 | Any solution |
| ≤ 60 % | 2,20 | 0,30 | 0,25 | Any solution |
| >60 % | 2,00 | 0,28 | 0,22 | Any solution |
© SABS 21
SANS 10400-XA:2021 Edition 2
5.3.6 To reduce the formation of condensation in the Southern Cape Condensation Problem Area (see figure 5 and table C.1) the U-values of fenestration shall be achieved by means other than single low emissivity glass to maintain the energy efficiency properties.
NOTE The use of single low emissivity glass increases condensation formation thereby negatively impacting the U value and causing the installation to fall short of its certified performance.
Figure 5 — The Southern Cape Condensation Problem Area (SCCP)
22 © SABS
SANS 10400-XA:2021
Edition 2
5.3.7 The maximum air leakage for windows and doors shall comply with the requirements of SANS 613.
5.3.8 Roof lights (sloped/horizontal glazing as shown in figure 6) serving a space in the building envelope shall:
a) be acceptable if the total area of roof lights is less or equal to 1,5 % of the floor area or space they serve;
b) comply with table 5 if the total area of roof lights is more than 1,5 % but not more than 10 % of the floor area or space they serve; and
c) achieve an SHGC of not more than 0,25 and a total U-value of not more than 2,0 W/m².K if the total area of roof lights is more than 10 % of the floor area of the room or space they serve.
NOTE The thermal performance of an imperforate ceiling diffuser may be included in the total U-value of a roof light.
Table 5 — Roof lights — thermal performance of fenestration
| 1 | 2 | 3 |
|---|---|---|
| Ratio fenestration/ space served |
U-Value (W/m².K) |
SHGC |
| <1,5 % | Any | Any |
| 1,5 % to ≤ 3% | ≤ 5,8 | ≤ 0,75 |
| >3 % to ≤ 5 % | ≤ 5,8 | ≤ 0,50 |
| >5 % to ≤ 10 % | ≤ 2,7 | ≤ 0,25 |
| >10 % | ≤ 2,0 | ≤ 0,25 |
© SABS 23
SANS 10400-XA:2021 Edition 2
5.4 Floors
Figure 6 — Defining a roof light
5.4.1 Where an underfloor heating system (for example, in-screed, under laminate heating, under carpet heating, under-tile heating, cut-in under floor heating, and water-based under floor heating) is installed, the floor shall be insulated with insulation that has a minimum R-value of not less than 1,0 m².K/W such as to prevent heat loss to the surrounding and adjacent ground.
5.4.2 A suspended floor that is part of a building’s envelope shall have insulation that will retain its thermal properties under moist conditions and be installed for
a) Energy zones 1, 2, 6 and 7 and shall achieve an insulation R-value of 1,5 m².K/W.
b) Energy zones 3 and 4, 5 and 5H and shall achieve an insulation R-value of 1,0 m².K/W.
5.5 External walls
5.5.1 The minimum total R-value requirements for an external wall for buildings other than category 1 buildings with a surface density equal or greater than 270 kg/m² shall be in accordance with table 6.
5.5.2 Single-leaf masonry walls in category 1 buildings shall have a nominal wall thickness greater than or equal to 140 mm.
NOTE Nominal wall thickness refers to the thickness of a wall excluding the thickness of any plaster applied.
5.5.3 Walls for buildings with a surface density less than 270 kg/m² shall achieve a minimum total R-value or a minimum CR-value (by the addition of capacity or resistance (or both)) shall be in accordance with table 7.
24 © SABS
SANS 10400-XA:2021
Edition 2
Table 6 — Minimum R-value requirements for walls with a surface density greater than or equal to 270 kg/m²
| 1 | 2 | 3 | 4 |
|---|---|---|---|
| Walls | Walls | Walls | Walls |
| Surface density | Energy zones | R-value (m2.K/W) |
Minimum requirementa |
| >270 kg/m2 | 1 | 0,6 | 50mm cavity wall |
| >270 kg/m2 | 2 | 0,6 | 50mm cavity wall |
| >270 kg/m2 | 3 | 0,4 | Collar jointed wall |
| >270 kg/m2 | 4 | 0,6 | 50mm cavity wall |
| >270 kg/m2 | 5 | 0,4 | Collar jointed wall |
| >270 kg/m2 | 5H | 0,4 | Collar jointed wall |
| >270 kg/m2 | 6 | 0,6 | 50mm cavity wall |
| >270 kg/m2 | 7 | 0,6 | 50mm cavity wall |
| aWalls built with FBX, FBS and FBA clay bricks and high-density concrete face bricks and blocks do not need to be plastered. All other walls need to be plastered internally and externally. |
aWalls built with FBX, FBS and FBA clay bricks and high-density concrete face bricks and blocks do not need to be plastered. All other walls need to be plastered internally and externally. |
aWalls built with FBX, FBS and FBA clay bricks and high-density concrete face bricks and blocks do not need to be plastered. All other walls need to be plastered internally and externally. |
aWalls built with FBX, FBS and FBA clay bricks and high-density concrete face bricks and blocks do not need to be plastered. All other walls need to be plastered internally and externally. |
Table 7 — Minimum R-value requirements or CR-value requirements for walls with a surface density less than 270 kg/m²
| 1 | 2 | 3 |
|---|---|---|
| Walls | Walls | Walls |
| Energy zones | R-Value (m²K/W) |
CR-Value (h) |
| 1 | 2,2 | 100 |
| 2 | 2,2 | 100 |
| 3 | 1,9 | 80 |
| 4 | 1,9 | 80 |
| 5 | 1,9 | 80 |
| 5H | 1,9 | 80 |
| 6 | 2,2 | 100 |
| 7 | 2,2 | 100 |
5.5.4 A walling construction that has any metal sheet, metal studs, metal tracks or metal battens fixed to each other shall have a thermal break consisting of a material with an R-value of not less than 0,2 m².K/W installed between the metal structural elements.
5.5.5 Spaces such as garages, enclosed verandahs, glasshouses, solariums, storerooms or pool enclosures to the main building (see figure 7) shall either be excluded from or be included in the building envelope but, where excluded, shall not compromise the thermal performance of the main building envelope.
© SABS 25
SANS 10400-XA:2021 Edition 2
5.6 Roof assembly
Figure 7 — Separation of attachments
5.6.1 Thermal insulation shall be installed so that it
a) abuts or overlaps adjoining insulation, or is sealed,
b) forms a continuous barrier with ceilings, walls, bulkheads, or floors that contribute to the thermal barrier, and
c) does not affect the safe or effective operation of any services, equipment, or lighting installation.
5.6.2 A roof assembly shall achieve the minimum total R-value of the specified requirement in table 8 for the direction of heat flow.
NOTE 1 R-values are calculated in accordance with the constants and generic conductance values of SANS 694 and the results when tested to SANS 8301
NOTE 2 Table 9 provides generic thermal resistance values considered to be achieved by reflective foil laminates.
5.6.3 A roof assembly that has flexible bulk insulation material installed between the underside of the cladding and the top of the supporting member for the cladding shall have a spacer system, the depth of the spacer system to be equal to the material thickness required, to eliminate the compression of flexible bulk insulation. (See annex F)
5.6.4 The total R-value of a roof assembly which incorporates a reflective surface and adjacent airspace, shall include the combined R-value achieved by the emittance of the reflective surface and the associated airspaces in accordance with table 9.
5.6.5 In a roof assembly that consists of thatch the thickness of the thatch shall be as follows:
a) Fine thatching grass or reed in all zones except 5H: 210 mm or R value of 3,7 m².K/W.
b) Fine thatching grass or reed in zone 5H: 175 mm or R value of 2,7 m².K/W.
c) Water reed: 300 mm.
26 © SABS
SANS 10400-XA:2021
Edition 2
NOTE 1 Fine thatching grass or reed has a stem/butt diameter between 1,4 mm and 4 mm.
NOTE 2 Water reed has a stem/butt diameter between 1 mm and 7 mm.
5.6.6 Bulk insulation shall be installed so that in ceilings, it overlaps the wall member by not less than 50 mm or is tightly fitted against a wall where there is no insulation in the wall.
NOTE Care should be taken when installing thermal insulation to ensure that it does not interfere with the safety or performance of domestic services and fittings such as heating flues, recessed light fittings, light transformers and general plumbing and electrical components.
© SABS 27
SANS 10400-XA:2021 Edition 2
Table 8 — Minimum total R-values of roofs assemblies and levels of thermal insulation
| 1 | Col2 | Col3 | 2 | Col5 | Col6 | Col7 |
|---|---|---|---|---|---|---|
| Description | Description | Description | Energy zones | Energy zones | Energy zones | Energy zones |
| Description | Description | Description | 1, 2, 4, 6, 7 | **3 ** | **5 ** | **5 ** |
| Description | Description | Description | 1, 2, 4, 6, 7 | **3 ** | **5 ** | 5H |
| Minimum required Total R-Value (m².K/W) |
Minimum required Total R-Value (m².K/W) |
Minimum required Total R-Value (m².K/W) |
3,7 | 3,7 | 3,7 | 2,7 |
| Direction of heat flow | Direction of heat flow | Direction of heat flow | Up | Up and Down | Down | Down |
| Minimum total R-value (m².K/W) of roof and ceiling materials (Roof covering includes outside air film, non-reflective unventilated air space and plasterboard only). |
Minimum total R-value (m².K/W) of roof and ceiling materials (Roof covering includes outside air film, non-reflective unventilated air space and plasterboard only). |
Minimum total R-value (m².K/W) of roof and ceiling materials (Roof covering includes outside air film, non-reflective unventilated air space and plasterboard only). |
0,30 to 0,35 | 0,30 to 0,35 | 0,36 to 0,48 | 0,36 to 0,48 |
| Estimated minimum added R-Value of insulation (m².K/W) |
Estimated minimum added R-Value of insulation (m².K/W) |
Estimated minimum added R-Value of insulation (m².K/W) |
3,35 | 3,35 | 3,35 | 2,35 |
| Product | Product | Product | Recommended levels (thickness in mm) of thermal insulation to be used equivalent to R-Value required. Thermal conductivity values used are generic. |
Recommended levels (thickness in mm) of thermal insulation to be used equivalent to R-Value required. Thermal conductivity values used are generic. |
Recommended levels (thickness in mm) of thermal insulation to be used equivalent to R-Value required. Thermal conductivity values used are generic. |
Recommended levels (thickness in mm) of thermal insulation to be used equivalent to R-Value required. Thermal conductivity values used are generic. |
| Generic insulation product | Density (kg/m³) |
K-value (W/m.K) |
mm | mm | mm | mm |
| Cellulose fibre bonded | 30,00 | 0,038 | 130 | 130 | 130 | 90 |
| Cellulose fibre loose-fill | 27,50 | 0,040 | 135 | 135 | 135 | 100 |
| Glass wool blanket | 10 to 18 | 0,040 | 135 | 135 | 135 | 100 |
| Polyester fibre blanket | 11,50 | 0,046 | 160 | 160 | 160 | 110 |
| Polyester fibre blend board | 24,00 | 0,038 | 130 | 130 | 130 | 90 |
| Expanded Polystyrene (EPS) Standard Density (SD) |
15,00 | 0,035a | 120 | 120 | 120 | 85 |
| Extruded Polystyrene (XPS) | 32,00 | 0,028a | 100 | 100 | 100 | 65 |
| Fibre glass board | 47,50 | 0,033 | 115 | 115 | 115 | 80 |
| Mineral/Rockwool | 40.00 to 140.00 | 0,033 | 115 | 115 | 115 | 80 |
| Polyester fibre blend board | 61,00 | 0,034 | 115 | 115 | 115 | 80 |
| Polyurethane and polyisocyanurate board |
32,00 | 0,025a | 85 | 85 | 85 | 60 |
| NOTE 1 Zone 5H high humidity to be considered. | NOTE 1 Zone 5H high humidity to be considered. | NOTE 1 Zone 5H high humidity to be considered. | NOTE 1 Zone 5H high humidity to be considered. | NOTE 1 Zone 5H high humidity to be considered. | NOTE 1 Zone 5H high humidity to be considered. | NOTE 1 Zone 5H high humidity to be considered. |
| NOTE 2 Thermal conductivity values used are generic. | NOTE 2 Thermal conductivity values used are generic. | NOTE 2 Thermal conductivity values used are generic. | NOTE 2 Thermal conductivity values used are generic. | NOTE 2 Thermal conductivity values used are generic. | NOTE 2 Thermal conductivity values used are generic. | NOTE 2 Thermal conductivity values used are generic. |
| NOTE 3 Manufacturers will round up thicknesses to nearest production standard. | NOTE 3 Manufacturers will round up thicknesses to nearest production standard. | NOTE 3 Manufacturers will round up thicknesses to nearest production standard. | NOTE 3 Manufacturers will round up thicknesses to nearest production standard. | NOTE 3 Manufacturers will round up thicknesses to nearest production standard. | NOTE 3 Manufacturers will round up thicknesses to nearest production standard. | NOTE 3 Manufacturers will round up thicknesses to nearest production standard. |
| aThermal efficiency is dependent on material thickness, blowing agent, density, age, operating temperature, and moisture. | aThermal efficiency is dependent on material thickness, blowing agent, density, age, operating temperature, and moisture. | aThermal efficiency is dependent on material thickness, blowing agent, density, age, operating temperature, and moisture. | aThermal efficiency is dependent on material thickness, blowing agent, density, age, operating temperature, and moisture. | aThermal efficiency is dependent on material thickness, blowing agent, density, age, operating temperature, and moisture. | aThermal efficiency is dependent on material thickness, blowing agent, density, age, operating temperature, and moisture. | aThermal efficiency is dependent on material thickness, blowing agent, density, age, operating temperature, and moisture. |
28 © SABS
SANS 10400-XA:2021
Edition 2
Table 9 — R-values considered to be achieved by reflective foil laminates
| 1 | 2 | 3 | Col4 | Col5 | Col6 | Col7 | Col8 |
|---|---|---|---|---|---|---|---|
| Emissivity of added reflective insulation |
Direction of heat flow |
R-value added by reflective insulation(m².K/W) | R-value added by reflective insulation(m².K/W) | R-value added by reflective insulation(m².K/W) | R-value added by reflective insulation(m².K/W) | R-value added by reflective insulation(m².K/W) | R-value added by reflective insulation(m².K/W) |
| Emissivity of added reflective insulation |
Direction of heat flow |
Pitched roof (≥ 10 º) with horizontal ceiling |
Pitched roof (≥ 10 º) with horizontal ceiling |
Flat skillion or pitched roof (≤ 10 º) with horizontal ceiling |
Pitched roof with cathedral ceilings | Pitched roof with cathedral ceilings | Pitched roof with cathedral ceilings |
| Emissivity of added reflective insulation |
Direction of heat flow |
Natural ventilated roof space |
Non- ventilated roof space |
Non- ventilated roof space |
22º | 30º | 45º |
| 0.2 outer 0.05 inner |
Downwards | 1,21 | 1,12 | 1,28 | 0,96 | 0,86 | 0,66 |
| 0.2 outer 0.05 inner |
Upwards | 0,59 | 0,75 | 0,68 | 0,72 | 0,74 | 0,77 |
| 0.9 outer 0.05 inner |
Downwards | 1,01 | 0,92 | 1,06 | 0,74 | 0,64 | 0,44 |
| 0.9 outer 0.05 inner |
Upwards | 0,40 | 0,55 | 0,49 | 0,51 | 0,52 | 0,53 |
| NOTE 1 This table is applicable where an air space between the external roof cladding and a ceiling assembly is divided by the positioning of a reflective foil to create two air gaps. Reflective foil insulation values include a minimum 15 mm air gap on either side. Reflective insulation should work in conjunction with an air gap to be effective. NOTE 2 The reflective surface with the lowest emissivity should preferably be facing downwards. NOTE 3 0.2 outer value is used where the roof is sealed, and no dust can accumulate. 0,9 outer value is used where dust can impair performance. Bright metal surfaces can generally be taken as 0,05 emissivity. NOTE 4 The R-value of reflective insulation is affected by the airspace between a reflective side of the reflective insulation and the building lining or cladding. The thermal performance of reflective insulation is influenced by dust and could be adversely affected. |
NOTE 1 This table is applicable where an air space between the external roof cladding and a ceiling assembly is divided by the positioning of a reflective foil to create two air gaps. Reflective foil insulation values include a minimum 15 mm air gap on either side. Reflective insulation should work in conjunction with an air gap to be effective. NOTE 2 The reflective surface with the lowest emissivity should preferably be facing downwards. NOTE 3 0.2 outer value is used where the roof is sealed, and no dust can accumulate. 0,9 outer value is used where dust can impair performance. Bright metal surfaces can generally be taken as 0,05 emissivity. NOTE 4 The R-value of reflective insulation is affected by the airspace between a reflective side of the reflective insulation and the building lining or cladding. The thermal performance of reflective insulation is influenced by dust and could be adversely affected. |
NOTE 1 This table is applicable where an air space between the external roof cladding and a ceiling assembly is divided by the positioning of a reflective foil to create two air gaps. Reflective foil insulation values include a minimum 15 mm air gap on either side. Reflective insulation should work in conjunction with an air gap to be effective. NOTE 2 The reflective surface with the lowest emissivity should preferably be facing downwards. NOTE 3 0.2 outer value is used where the roof is sealed, and no dust can accumulate. 0,9 outer value is used where dust can impair performance. Bright metal surfaces can generally be taken as 0,05 emissivity. NOTE 4 The R-value of reflective insulation is affected by the airspace between a reflective side of the reflective insulation and the building lining or cladding. The thermal performance of reflective insulation is influenced by dust and could be adversely affected. |
NOTE 1 This table is applicable where an air space between the external roof cladding and a ceiling assembly is divided by the positioning of a reflective foil to create two air gaps. Reflective foil insulation values include a minimum 15 mm air gap on either side. Reflective insulation should work in conjunction with an air gap to be effective. NOTE 2 The reflective surface with the lowest emissivity should preferably be facing downwards. NOTE 3 0.2 outer value is used where the roof is sealed, and no dust can accumulate. 0,9 outer value is used where dust can impair performance. Bright metal surfaces can generally be taken as 0,05 emissivity. NOTE 4 The R-value of reflective insulation is affected by the airspace between a reflective side of the reflective insulation and the building lining or cladding. The thermal performance of reflective insulation is influenced by dust and could be adversely affected. |
NOTE 1 This table is applicable where an air space between the external roof cladding and a ceiling assembly is divided by the positioning of a reflective foil to create two air gaps. Reflective foil insulation values include a minimum 15 mm air gap on either side. Reflective insulation should work in conjunction with an air gap to be effective. NOTE 2 The reflective surface with the lowest emissivity should preferably be facing downwards. NOTE 3 0.2 outer value is used where the roof is sealed, and no dust can accumulate. 0,9 outer value is used where dust can impair performance. Bright metal surfaces can generally be taken as 0,05 emissivity. NOTE 4 The R-value of reflective insulation is affected by the airspace between a reflective side of the reflective insulation and the building lining or cladding. The thermal performance of reflective insulation is influenced by dust and could be adversely affected. |
NOTE 1 This table is applicable where an air space between the external roof cladding and a ceiling assembly is divided by the positioning of a reflective foil to create two air gaps. Reflective foil insulation values include a minimum 15 mm air gap on either side. Reflective insulation should work in conjunction with an air gap to be effective. NOTE 2 The reflective surface with the lowest emissivity should preferably be facing downwards. NOTE 3 0.2 outer value is used where the roof is sealed, and no dust can accumulate. 0,9 outer value is used where dust can impair performance. Bright metal surfaces can generally be taken as 0,05 emissivity. NOTE 4 The R-value of reflective insulation is affected by the airspace between a reflective side of the reflective insulation and the building lining or cladding. The thermal performance of reflective insulation is influenced by dust and could be adversely affected. |
NOTE 1 This table is applicable where an air space between the external roof cladding and a ceiling assembly is divided by the positioning of a reflective foil to create two air gaps. Reflective foil insulation values include a minimum 15 mm air gap on either side. Reflective insulation should work in conjunction with an air gap to be effective. NOTE 2 The reflective surface with the lowest emissivity should preferably be facing downwards. NOTE 3 0.2 outer value is used where the roof is sealed, and no dust can accumulate. 0,9 outer value is used where dust can impair performance. Bright metal surfaces can generally be taken as 0,05 emissivity. NOTE 4 The R-value of reflective insulation is affected by the airspace between a reflective side of the reflective insulation and the building lining or cladding. The thermal performance of reflective insulation is influenced by dust and could be adversely affected. |
NOTE 1 This table is applicable where an air space between the external roof cladding and a ceiling assembly is divided by the positioning of a reflective foil to create two air gaps. Reflective foil insulation values include a minimum 15 mm air gap on either side. Reflective insulation should work in conjunction with an air gap to be effective. NOTE 2 The reflective surface with the lowest emissivity should preferably be facing downwards. NOTE 3 0.2 outer value is used where the roof is sealed, and no dust can accumulate. 0,9 outer value is used where dust can impair performance. Bright metal surfaces can generally be taken as 0,05 emissivity. NOTE 4 The R-value of reflective insulation is affected by the airspace between a reflective side of the reflective insulation and the building lining or cladding. The thermal performance of reflective insulation is influenced by dust and could be adversely affected. |
5.7 Building sealing
5.7.1 Roofs, external walls, and floors that form the building envelope and any opening such as windows and doors in the external fabric shall be constructed to minimize air leakage.
NOTE The building sealing can be done by methods such as caulking, or adding skirting, architraves, or cornices.
5.7.2 Ceiling voids and attics, with the exception of thatched roofs, in all energy zones except energy zone 5H, where the building is naturally ventilated, the building shall be designed to minimize air infiltration. Accordingly, wall plate and roof junctions shall be sealed. All tiled roofs shall have a tile underlay or radiant barrier.
5.7.3 The chimney or flue of an open solid fuel burning appliance shall be provided with a damper or flap that can be closed to seal the chimney or flue.
NOTE A solid fuel burning device is a heater that burns material such as timber or coal. This does not apply to gas and liquid fuel burning devices.
5.7.4 A foam or rubber compressible strip or a fibrous seal to restrict air leakage shall be fitted to each edge of an external door and other such opening that
a) serves a conditioned space, or
b) serves a habitable room.
© SABS 29
SANS 10400-XA:2021 Edition 2
6 Services
6.1 Hot water supply
NOTE 1 The following types of water heating technology may be used to meet the requirements of Regulation XA:
a) Domestic solar water heaters that comply with 6.1.2;
b) Domestic heat pumps that comply with 6.1.3;
c) Sustainably sourced timber and invasive vegetation;
d) Biogas;
e) Natural gas;
f) Liquid Petroleum Gas; and
g) Heat recovery from building or external processes.
NOTE 2 If electrical resistance heating elements are used to supplement the above listed technologies, the supplementary heating may be used only to the extent of 50% of the annual average hot water requirements by volume.
NOTE 3 Unless preventative measures are taken the energy efficiency ratio (EER) of the system may drop below the 50% (EER=0,5) level and reach as low as 20% (EER=0,2).
NOTE 4 The EER of a solar hot water system may be boosted by (inter alia) increasing the volume of water stored to beyond the minimum volume specifications of table 10 and by specifying an electronic timer/controller.
6.1.1 Minimum storage capacities for hot water cylinders used with domestic solar water heaters and domestic heat pumps are provided in table 10.
6.1.2 Domestic solar water heaters shall comply with the requirements of SANS 1307 and shall be installed in accordance with SANS 10106.
6.1.3 Domestic hot water heat pumps shall comply with the requirements of SANS 1687 and shall be installed in accordance with SANS 1352.
6.1.4 Instantaneous gas water heaters shall comply with the requirements of SANS 1808-24 and SANS 1539 and shall be installed in accordance with SANS 10252-1 and SANS 10087-1.
6.1.5 Storage gas water heaters shall comply with the requirements of SANS 151, SANS 1808-24 and SANS 1539 and shall be installed in accordance with SANS 10254 and SANS 10087-1.
6.1.6 All exposed pipes to indoor or outdoor air, conveying hot water to and from the hot water cylinders and heating systems, shall be insulated with pipe insulation material with an R-value in accordance with table 11.
6.1.7 Piping to be insulated includes all supply and return hot water piping, cold water supply piping within 1 m of the connection to the heating or cooling system and pressure relief piping within 1 m of the connection to the heating or cooling system.
30 © SABS
SANS 10400-XA:2021
Edition 2
Table 10 — Minimum storage requirement for hot water cylinders used with domestic solar water heaters and domestic
heat pumps (stored at 60 ºC for health reasons)
| 1 | 2 | 3 | 4 |
|---|---|---|---|
| Occupancy description and application of hot water |
Occupancy classification |
Average annual hot water usage per capita per day (at 60 °C) |
24 h water storage requirement in litres at 60 ºC minimum temperature (for solar water heaters storage volumes shall be 50 % larger) |
| Entertainment and public assembly |
A1 | ||
| Sedentary | Sedentary | 10 L/p/d | 6 L/p |
| Active | Active | 40 L/p/d | 25 L/d |
| Theatrical and indoor sport | A2 | ||
| Cultural activities | Cultural activities | 10 L/p/d | 6 L/p |
| Sporting activities | Sporting activities | 40 L/p/d | 25 L/d |
| Places of instruction | A3 | 10 L/p/d | 6 L/p |
| Places of detention | E1 | ||
| Awaiting trial | Awaiting trial | 140 L/p/d | 62.5 L/p |
| Convicted | Convicted | 52 L/p/d | 35 L/p |
| Hospitals (including clinics) | E2 | ||
| General hospitals | General hospitals | 130 L/p/d | 30 L/p |
| Clinic with beds (overnight stay) | Clinic with beds (overnight stay) | 130 L/p/d | 30 L/p |
| Day hospital | Day hospital | 65 L/p/d | 18 L/p |
| Day clinic | Day clinic | 10 L/p/d | 6 L/p |
© SABS 31
SANS 10400-XA:2021 Edition 2
| Table 10 (concluded) | Col2 | Col3 | Col4 |
|---|---|---|---|
| 1 | 2 | 3 | 4 |
| Occupancy description and application of hot water |
Occupancy classification |
Average annual usage per capita per day (at 60 °C) |
24 h water storage requirement in litres at 60 ºC minimum temperature (for solar water heaters storage volumes shall be 50 % larger) |
| Other institutional (residential) |
E3 | 120 L/p/d | 75 L/p |
| Health care | E4 | 120 L/p/d | 75 L/p |
| Large shop | F1 | 10 L/p/d | 6 L/p |
| Small shop | F2 | 10 L/p/d | 6 L/p |
| Wholesaler’s store | F3 | 10 L/p/d | 6 L/p |
| Offices | G1 | ||
| Without canteens | 10 L/p/d | 6 L/p | |
| With canteens | 28 L/p/d | 20 L/p | |
| Hotels | H1 | 140 L/p/d | 62.5 L/p |
| Dormitory | H2 | 100 L/p/d | 50 L/p |
| Residential | H3 | ||
| Category 1 | 64 L/p/d | 45 L/p | |
| Retirement village residential units |
52 L/p/d | 35 L/p | |
| All other | 115 L/p/d | 50 L/p | |
| Dwelling house | H4 | ||
| Category 1 | 64 L/p/d | 45 L/p | |
| All other | 115 L/p/d | 50 L/p | |
| Hospitality | H5 | 140 L/p/d | 62.5 L/p |
32 © SABS
SANS 10400-XA:2021
Edition 2
Table 11 — Minimum R-value of pipe insulation
6.2 Lighting
| 1 | 2 |
|---|---|
| Internal diameter of pipe mm |
Minimum R-value m².K/W |
| ≤ 80 | 1,00 |
| >80 | 1,50 |
| NOTE R-values in this table are based on the formula for flat surfaces i.e. R-value = m/k-value where (m) denotes thickness |
NOTE R-values in this table are based on the formula for flat surfaces i.e. R-value = m/k-value where (m) denotes thickness |
6.2.1 The lighting power density for all lighting as calculated by aggregating the connected lighting energy demand per occupancy and dividing this total by the net floor area for the relevant occupancy shall not exceed the lighting power density values set out in table 12.
NOTE Connected lighting includes internal and external lighting arrangements served by the electrical supply of the building
6.2.2 The use of light-emitting diodes (LED) and compact fluorescents (CFL) in occupancies H3 and H4 shall be deemed to comply with the requirements of 6.2.1. Any other lighting technologies used in occupancies H3 and H4 shall not exceed the lighting power density values set out in table 12.
6.2.3 Occupancy and daylight sensors shall be installed in occupancies, excluding those classified as H3 and H4 in terms of Regulation A20, and these occupancy and daylight sensors shall be so installed that no area serviced by a specific sensor is more than 100 m².
Table 12 — Maximum lighting power density for the class of occupancy
| 1 | 2 | 3 |
|---|---|---|
| Occupancy classification |
Occupancy description | Lighting power density W/m² |
| A1 | Entertainment and public assembly | 2 |
| A2 | Theatrical and indoor sport | 8 |
| A3 | Places of instruction | 10 |
| A4 | Worship | 4 |
| C1 | Exhibition halls | 10 |
| C2 | Museums | 4 |
| E1 | Places of detention | 4 |
| E2 | Hospital | 8 |
| E3 | Other institutional residences | 8 |
| E4 | Health care | 8 |
© SABS 33
SANS 10400-XA:2021 Edition 2
| (concluded) | Col2 | Col3 |
|---|---|---|
| 1 | 2 | 3 |
| Occupancy classification |
Occupancy description | Lighting power density W/m² |
| F1 | Large shops | 20 |
| F2 | Small shops | 8 |
| F3 | Wholesale store | 8 |
| G1 | Offices | 8 |
| H1 | Hotels | 4 |
| H2 | Dormitory | 4 |
| H3 | Domestic residences | 4 |
| H4 | Dwelling houses | 4 |
| H5 | Hospitality | 4 |
6.3 Air conditioning
The minimum required level of energy efficiency for unitary and packaged air-conditioning equipment shall be in accordance with table 13.
| Table 13 — Mi heating mode (C | inimum coefficient of per COPH) of unitary and pac | rformance, cooling mode (C ckaged air-conditioning equ | COPC), uipment |
|---|---|---|---|
| 1 | 2 | 3 | 4 |
| Equipment type | Capacity range **(kW)a ** |
**Minimum COPC ** | **Minimum COPH ** |
| Through-the-wall consolesa | <7 | 2,8 | 1,0 |
| Unitary splitsb | <7 | 3,0 | 3,2 |
| Air-cooled packaged and split unitsc | 7 < 19 | 2,9 | 3,0 |
| Air-cooled packaged and split unitsc | 19 < 40 | 2,9 | 3,0 |
| Air-cooled packaged and split unitsc | 40 < 70 | 2,8 | 2,9 |
| Air-cooled packaged and split unitsc | >70 | 2,7 | 2,8 |
| Water-cooled packaged unitsd | <19 | 3,3 | 3,5 |
| Water-cooled packaged unitsd | 19 < 40 | 3,3 | 3,5 |
| Water-cooled packaged unitsd | 40 < 70 | 3,2 | 3,3 |
| Water-cooled packaged unitsd | 70 < 223 | 3,2 | 3,3 |
34 © SABS
SANS 10400-XA:2021
Edition 2
| Table 13 (concluded) | Col2 | Col3 | Col4 |
|---|---|---|---|
| 1 | 2 | 3 | 4 |
| Equipment type | Capacity range **(kW)a ** |
**Minimum COPC ** | **Minimum COPH ** |
| Air-cooled water chillersd | All | 2,8 | – |
| Air-cooled heat pump chillersd | All | 2,8 | 3,0 |
| Water-cooled, positive displacement water chillersd |
<264 | 4,3 | – |
| Water-cooled, positive displacement water chillersd |
264 < 528 | 4,4 | – |
| Water-cooled, positive displacement water chillersd |
528 < 1 055 | 4,9 | – |
| Water-cooled, positive displacement water chillersd |
>1 055 | 5,4 | – |
| Water-cooled, centrifugal water chillersd |
<528 | 5,3 | – |
| Water-cooled, centrifugal water chillersd |
528 < 1 055 | 5,3 | – |
| Water-cooled, centrifugal water chillersd |
1 055 < 2 110 | 5,9 | – |
| Water-cooled, centrifugal water chillersd |
>2 110 | 5,9 | – |
| aIf resistance heating is used, heating power consumption shall not exceed cooling power consumption except in the case of equipment of <10 kW. b COPC and COPH shall be determined at the temperatures stipulated in SANS 54511-2 and in accordance with SANS 5151. c COPC and COPH shall be determined at the temperatures stipulated in SANS 54511-2 and in accordance with SANS 13253. d COPC and COPH shall be determined at the temperatures stipulated in SANS 54511-2 and in accordance with SANS 54511-3. |
aIf resistance heating is used, heating power consumption shall not exceed cooling power consumption except in the case of equipment of <10 kW. b COPC and COPH shall be determined at the temperatures stipulated in SANS 54511-2 and in accordance with SANS 5151. c COPC and COPH shall be determined at the temperatures stipulated in SANS 54511-2 and in accordance with SANS 13253. d COPC and COPH shall be determined at the temperatures stipulated in SANS 54511-2 and in accordance with SANS 54511-3. |
aIf resistance heating is used, heating power consumption shall not exceed cooling power consumption except in the case of equipment of <10 kW. b COPC and COPH shall be determined at the temperatures stipulated in SANS 54511-2 and in accordance with SANS 5151. c COPC and COPH shall be determined at the temperatures stipulated in SANS 54511-2 and in accordance with SANS 13253. d COPC and COPH shall be determined at the temperatures stipulated in SANS 54511-2 and in accordance with SANS 54511-3. |
aIf resistance heating is used, heating power consumption shall not exceed cooling power consumption except in the case of equipment of <10 kW. b COPC and COPH shall be determined at the temperatures stipulated in SANS 54511-2 and in accordance with SANS 5151. c COPC and COPH shall be determined at the temperatures stipulated in SANS 54511-2 and in accordance with SANS 13253. d COPC and COPH shall be determined at the temperatures stipulated in SANS 54511-2 and in accordance with SANS 54511-3. |
© SABS 35
SANS 10400-XA:2021 Edition 2
Annex A
(informative)
South African Energy Trajectory A.1 The Draft National Energy Efficiency Strategy published by the Department of Energy
(Government Gazette, 23 December 2016), identifies the need to establish 15-year trajectories for the successive tightening of the energy performance component of building standards for the public, commercial and residential building sectors.
A.2 Subject to any other corrections that may be applied to table 2, future revisions to this part of
SANS 10400 will be guided by the intended energy trajectory in table A.1.
NOTE The Energy Trajectory is adapted from the proposal for a revision and extension of table 2 of SANS 204:2011; Solid Green, for GIZ, May 2015.
A.3 The proposed Energy trajectory is to achieve 8 % reduction on previous maximum energy
demand and maximum annual consumption every two years.
A.4 The intended energy trajectory normalized to 2021 is given in table A.1
Table A.1 — Intended energy trajectory normalized to 2021
| 1 | 2 |
|---|---|
| Year | Percentage normalized to 2021 |
| Year 2021 and 2022 | 92 % |
| Year 2023 and 2024 | 85 % |
| Year 2025 and 2026 | 78 % |
| Year 2027 and 2028 | 72 % |
| Year 2029 and 2030 | 66 % |
36 © SABS
SANS 10400-XA:2021
Edition 2
Annex B
(normative)
Modelling conditions B.1 Where the theoretical annual energy consumption of a building (excluding garages and storage
areas) is calculated the following modelling assumptions shall be used:
a) the design population shall be accordance with National building Regulation A21;
b) artificial lighting shall be accordance with table 12;
c) the space temperature shall be within the range of 19 °C to 25 °C for a minimum of 95 % of occupied hours; and
d) artificial ventilation, heating and cooling provided, shall be in accordance with the requirements of SANS 10400-O.
B.2 The internal heat gains to be built into the energy model shall be as set follows
a) the design population calculated in accordance with National Building Regulation A21 at an average rate of 75 W sensible heat gain per person,
b) hot meals in a dining room, restaurant, or café, at a rate of 30 W heat gain per person with the number of people calculated in accordance with National Building Regulation A21,
c) Appliances and equipment shall be in accordance with table B.1, and
d) lighting, occupancy and plug loads calculated with utilization hours and usage ratios shall be in accordance with table B.2.
B.3 Hot water shall be supplied at the consumption rates in accordance with table 10 and equipment
designed to maintain and supply the water storage temperature at 60 °C.
Table B.1 — Internal heat gains for appliances and equipment
| 1 | 2 |
|---|---|
| Classification of occupancy of buildings | Internal heat gain W/m² |
| G1 | 15 |
| F1 | 5 |
| Other occupancies | No load |
© SABS 37
SANS 10400-XA:2021 Edition 2
Table B.2 — Design utilization rates
| 1 | 2 | 3 | 4 | 5 | 6 |
|---|---|---|---|---|---|
| Occupancies A1, A2, A3 | Occupancies A1, A2, A3 | Occupancies A1, A2, A3 | Occupancies A1, A2, A3 | Occupancies A1, A2, A3 | Occupancies A1, A2, A3 |
| Occupancy hours of the day | 0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-00:00 |
| Weekdays | 0,48 | 1 | 0,66 | 0,25 | 0,05 |
| Saturday | 0,4 | 0,15 | 0,3 | 0,2 | 0,1 |
| Sunday & holiday | 0,2 | 0,08 | 0,15 | 0,1 | 0,05 |
| Lighting, occupancy and plug loads | 0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-00:00 |
| Weekdays | 0,48 | 1 | 0,66 | 0,25 | 0,05 |
| Saturday | 0,4 | 0,15 | 0,3 | 0,2 | 0,1 |
| Sunday & holiday | 0,2 | 0,08 | 0,15 | 0,1 | 0,05 |
| Occupancies E1, E2, E3 | Occupancies E1, E2, E3 | Occupancies E1, E2, E3 | Occupancies E1, E2, E3 | Occupancies E1, E2, E3 | Occupancies E1, E2, E3 |
| Occupancy hours of the day | 0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-00:00 |
| Weekdays | 0,35 | 0,8 | 0,8 | 0,65 | 0,2 |
| Saturday | 0,35 | 0,8 | 0,8 | 0,65 | 0,2 |
| Sunday & holiday | 0,23 | 0,53 | 0,53 | 0,43 | 0,13 |
| Lighting, occupancy, and equipment plug loads |
0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-00:00 |
| Weekdays | 0,35 | 0,8 | 0,8 | 0,65 | 0,2 |
| Saturday | 0,35 | 0,8 | 0,8 | 0,65 | 0,2 |
| Sunday & holiday | 0,23 | 0,53 | 0,53 | 0,43 | 0,13 |
| Occupancies F1, F2, F3 | Occupancies F1, F2, F3 | Occupancies F1, F2, F3 | Occupancies F1, F2, F3 | Occupancies F1, F2, F3 | Occupancies F1, F2, F3 |
| Occupancy hours of the day | 0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-00:00 |
| Weekdays | 0,03 | 0,8 | 0,8 | 0,3 | 0 |
| Saturday | 0,03 | 0,8 | 0,66 | 0 | 0 |
| Sunday & holiday | 0,01 | 0,4 | 0,33 | 0 | 0 |
| Lighting, occupancy, and equipment plug loads |
0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-00:00 |
| Weekdays | 0,07 | 0,8 | 0,8 | 0,31 | 0,05 |
| Saturday | 0,07 | 0,8 | 0,61 | 0,05 | 0,05 |
| Sunday & holiday | 0,07 | 0,8 | 0,61 | 0,05 | 0,05 |
38 © SABS
SANS 10400-XA:2021
Edition 2
| Table B.2 (continued) | Col2 | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| Occupancy G1 | Occupancy G1 | Occupancy G1 | Occupancy G1 | Occupancy G1 | Occupancy G1 |
| Occupancy hours of the day | 0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-24:00 |
| Weekdays | 0,13 | 0,8 | 0,77 | 0,23 | 0 |
| Saturday | 0,08 | 0,5 | 0,37 | 0 | 0 |
| Sunday & holiday | 0,04 | 0,25 | 0,19 | 0 | 0 |
| Lighting, occupancy, and equipment plug loads |
0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-24:00 |
| Weekdays | 0,16 | 0,8 | 0,77 | 0,24 | 0,05 |
| Saturday | 0,11 | 0,5 | 0,38 | 0,05 | 0,05 |
| Sunday & holiday | 0,11 | 0,5 | 0,38 | 0,05 | 0,05 |
| Lighting, occupancy, and equipment plug loads |
0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-24:00 |
| Weekdays | 0,16 | 0,35 | 0,77 | 0,24 | 0,05 |
| Saturday | 0,11 | 0,5 | 0,38 | 0,05 | 0,05 |
| Sunday & holiday | 0,11 | 0,5 | 0,38 | 0,05 | 0,05 |
| Occupancies H2, H3, H4 | Occupancies H2, H3, H4 | Occupancies H2, H3, H4 | Occupancies H2, H3, H4 | Occupancies H2, H3, H4 | Occupancies H2, H3, H4 |
| Occupancy hours of the day | 0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-24:00 |
| Weekdays | 0,88 | 0,37 | 0,36 | 0,73 | 1 |
| Saturday | 1 | 0,43 | 0,43 | 0,97 | 1 |
| Sunday & holiday | 1 | 0,43 | 0,43 | 0,97 | 1 |
| Lighting | 0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-24:00 |
| Weekdays | 0,13 | 0,13 | 0,14 | 0,24 | 0,1 |
| Saturday | 0,09 | 0,2 | 0,14 | 0,3 | 0,18 |
| Sunday & holiday | 0,09 | 0,2 | 0,14 | 0,3 | 0,18 |
| Equipment Plug load | 0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-24:00 |
| Weekdays | 0,53 | 0,57 | 0,59 | 0,78 | 0,6 |
| Saturday | 0,53 | 0,57 | 0,59 | 0,78 | 0,6 |
| Sunday & holiday | 0,53 | 0,57 | 0,59 | 0,78 | 0,6 |
© SABS 39
SANS 10400-XA:2021 Edition 2
| Table B.2 (concluded) | Col2 | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| Occupancies H1, H5 | Occupancies H1, H5 | Occupancies H1, H5 | Occupancies H1, H5 | Occupancies H1, H5 | Occupancies H1, H5 |
| Occupancy hours of the day | 0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-24:00 |
| Weekdays | 0,88 | 0,27 | 0,3 | 0,7 | 0,9 |
| Saturday | 0,8 | 0,33 | 0,34 | 0,85 | 0,75 |
| Sunday & holiday | 0,4 | 0,17 | 0,17 | 0,43 | 0,38 |
| Lighting | 0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-24:00 |
| Weekdays | 0,22 | 0,35 | 0,26 | 0,78 | 0,45 |
| Saturday | 0,18 | 0,35 | 0,26 | 0,68 | 0,45 |
| Sunday & holiday | 0,18 | 0,35 | 0,26 | 0,68 | 0,45 |
| Equipment Plug load | 0:00-08:00 | 08:00-11:00 | 11:00-18:00 | 18:00-22:00 | 22:00-24:00 |
| Weekdays | 0,53 | 0,57 | 0,59 | 0,78 | 0,6 |
| Saturday | 0,53 | 0,57 | 0,59 | 0,78 | 0,6 |
| Sunday & holiday | 0,53 | 0,57 | 0,59 | 0,78 | 0,6 |
40 © SABS
SANS 10400-XA:2021
Edition 2
Annex C
(informative)
List of cities and towns by energy zones
Table C.1 provides a list of cities and towns indicating their Energy zone, longitude, and latitude as well if it falls into the Southern Cape Condensation Problem Area (SCCP) to be used in conjunction with figure 1 and relevant clauses.
Table C.1 — List of cities and towns by energy zones
| 1 | 2 | 3 | 4 | 5 | 6 |
|---|---|---|---|---|---|
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Aberdeen | Eastern Cape | 24.062 | 32.476 | 1 | No |
| Acornhoek | Mpumalanga | 31.005 | 24.597 | 5 | No |
| Addo | Eastern Cape | 25.690 | 33.541 | 5 | Yes |
| Adelaide | Eastern Cape | 26.293 | 32.706 | 2 | No |
| Adendorp | Eastern Cape | 25.551 | 32.301 | 1 | No |
| Albertinia | Western Cape | 21.568 | 34.197 | 4 | Yes |
| Alexander Bay | Northern Cape | 16.491 | 28.609 | 4 | No |
| Alexandria | Eastern Cape | 26.412 | 33.654 | 4 | Yes |
| Algoa Bay | Eastern Cape | 25.795 | 33.826 | 5 | No |
| Alice | Eastern Cape | 26.828 | 32.778 | 4 | No |
| Alicedale | Eastern Cape | 26.082 | 33.317 | 4 | Yes |
| Aliwal North | Eastern Cape | 26.709 | 30.688 | 2 | No |
| Allanridge | Free State | 26.644 | 27.754 | 1 | No |
| Amatikulu | KwaZulu-Natal | 31.532 | 29.043 | 5H | No |
| Amersfoort | Mpumalanga | 29.870 | 27.005 | 2 | No |
| Arlington | Free State | 27.852 | 28.029 | 2 | No |
| Asbesberge | Northern Cape | 23.167 | 28.812 | 1 | No |
| Ashton | Western Cape | 20.053 | 33.835 | 1 | No |
| Askham | Northern Cape | 20.782 | 26.983 | 3 | No |
| Augrabies Falls | Northern Cape | 20.340 | 28.591 | 3 | No |
© SABS 41
SANS 10400-XA:2021 Edition 2
| Table C.1 (continued) | Col2 | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Barberton | Mpumalanga | 31.055 | 25.790 | 5 | No |
| Barkly East | Eastern Cape | 27.594 | 30.967 | 6 | No |
| Barkly West | Northern Cape | 24.524 | 28.537 | 1 | No |
| Baroe | Eastern Cape | 24.566 | 33.225 | 1 | No |
| Bathurst | Eastern Cape | 26.821 | 33.503 | 5 | Yes |
| Beaufort West | Western Cape | 22.586 | 33.341 | 1 | No |
| Bedford | Eastern Cape | 26.078 | 32.678 | 2 | No |
| Beestekraal | Northern Cape | 27.597 | 25.375 | 5 | No |
| Belfast | Mpumalanga | 31.569 | 24.491 | 5 | No |
| Bergville | KwaZulu-Natal | 29.345 | 28.731 | 2 | No |
| Bethal | Mpumalanga | 29.463 | 26.454 | 2 | No |
| Bethlehem | Free State | 28.303 | 28.231 | 2 | No |
| Bethulie | Free State | 25.976 | 30.495 | 1 | No |
| Biesiesfontein | Western Cape | 17.883 | 31.016 | 5 | No |
| Bisho | Eastern Cape | 27.441 | 32.848 | 4 | No |
| Bitterfontein | Western Cape | 18.265 | 31.041 | 5 | No |
| Bizana | Eastern Cape | 29.854 | 30.858 | 2 | No |
| Bloemfontein | Free State | 26.218 | 29.113 | 1 | No |
| Bloemhof | North West | 25.602 | 27.652 | 1 | No |
| Boshof | Free State | 25.240 | 28.540 | 1 | No |
| Bothaville | Free State | 26.567 | 27.394 | 1 | No |
| Brandfort | Free State | 26.455 | 28.702 | 1 | No |
| Brandvlei | Northern Cape | 20.479 | 30.466 | 1 | No |
| Bredasdorp | Western Cape | 20.040 | 34.532 | 4 | Yes |
42 © SABS
SANS 10400-XA:2021
Edition 2
| Table C.1 (continu | ued) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 2 | 3 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Breyten | Mpumalanga | 29.989 | 26.302 | 2 | No |
| Brits | North West | 27.781 | 25.630 | 5 | No |
| Britstown | Northern Cape | 23.502 | 30.590 | 1 | No |
| Bronkhorstspruit | Gauteng | 28.743 | 25.809 | 1 | No |
| Bultfontein | Free State | 26.147 | 28.287 | 1 | No |
| Burgersdorp | Eastern Cape | 26.331 | 30.996 | 6 | No |
| Butterworth | Eastern Cape | 28.141 | 32.330 | 4 | No |
| Caledon | Western Cape | 19.429 | 34.231 | 2 | Yes |
| Calitzdorp | Western Cape | 21.688 | 33.530 | 2 | No |
| Calvinia | Northern Cape | 19.775 | 31.473 | 1 | No |
| Campbell | Northern Cape | 23.723 | 28.799 | 1 | No |
| Cape Agulhas | Western Cape | 20.041 | 34.531 | 4 | Yes |
| Cape Town | Western Cape | 18.423 | 33.915 | 4 | Yes |
| Carletonville | Gauteng | 27.395 | 26.368 | 1 | No |
| Carnarvon | Northern Cape | 22.127 | 30.969 | 1 | No |
| Cathcart | Eastern Cape | 27.141 | 32.297 | 2 | No |
| Cedarville | Eastern Cape | 29.038 | 30.387 | 6 | No |
| Ceres | Western Cape | 19.311 | 33.369 | 2 | Yes |
| Charlestown | KwaZulu-Natal | 29.877 | 27.407 | 2 | No |
| Christiana | North West | 25.167 | 27.913 | 1 | No |
| Citrusdal | Western Cape | 19.016 | 32.594 | 1 | No |
| Clanwilliam | Western Cape | 18.891 | 32.175 | 5 | No |
| Clocolan | Free State | 27.568 | 28.915 | 2 | No |
© SABS 43
SANS 10400-XA:2021 Edition 2
| Table C.1 (co | ontinued) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Colenso | KwaZulu-Natal | 29.823 | 28.745 | 5 | No |
| Colesberg | Northern Cape | 25.108 | 30.707 | 1 | No |
| Coligny | North West | 26.319 | 26.311 | 1 | No |
| Cookhouse | Eastern Cape | 25.803 | 32.748 | 2 | No |
| Cradock | Eastern Cape | 25.618 | 32.170 | 2 | No |
| Danielskuil | Northern Cape | 23.548 | 28.186 | 1 | No |
| Dannhauser | KwaZulu-Natal | 30.060 | 28.014 | 1 | No |
| Darlington | Eastern Cape | 25.547 | 32.463 | 2 | No |
| Darnall | KwaZulu-Natal | 31.349 | 29.268 | 5H | No |
| De Aar | Northern Cape | 24.011 | 30.650 | 1 | No |
| Dealesville | Free State | 25.767 | 28.674 | 1 | No |
| Delareyville | North West | 25.444 | 26.688 | 5 | No |
| Delportshoop | Northern Cape | 24.310 | 28.415 | 1 | No |
| Derdepoort | North West | 26.387 | 24.639 | 5 | No |
| Dewetsdorp | Free State | 26.664 | 29.582 | 2 | No |
| Dimabaza | Eastern Cape | 27.223 | 32.837 | 4 | No |
| Donnybrook | KwaZulu-Natal | 29.879 | 29.928 | 2 | No |
| Dordrecht | Eastern Cape | 27.047 | 313.377 | 6 | No |
| Doringbos | Western Cape | 19.220 | 31.971 | 5 | No |
| Douglas | Northern Cape | 23.773 | 29.052 | 1 | No |
| Duiwelskloof | Limpopo | 30.144 | 23.695 | 5 | No |
44 © SABS
SANS 10400-XA:2021
Edition 2
| Table C.1 (cont | tinued) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Dullstroom | Mpumalanga | 30.102 | 25.417 | 2 | No |
| Durban | KwaZulu-Natal | 31.026 | 29.847 | 5H | No |
| East London | Eastern Cape | 27.903 | 33.014 | 5 | No |
| Edenburg | Gauteng | 28.061 | 26.051 | 1 | No |
| Edenville | Free State | 27.668 | 27.555 | 2 | No |
| Elliot | Eastern Cape | 27.883 | 31.333 | 6 | No |
| Elliotdale | Eastern Cape | 28.684 | 31.966 | 5 | No |
| Emalahleni | Mpumalanga | 29.211 | 25.872 | 2 | No |
| Emmaus | KwaZulu-Natal | 29.401 | 28.860 | 2 | No |
| Empangeni | KwaZulu-Natal | 31.889 | 28.741 | 5H | No |
| Engcobo | Eastern Cape | 28.002 | 31.673 | 2 | No |
| Erfenisdam | Free State | 26.782 | 28.502 | 1 | No |
| Ermelo | Mpumalanga | 29.987 | 26.525 | 2 | No |
| Eshowe | KwaZulu-Natal | 31.475 | 28.890 | 5H | No |
| Estcourt | KwaZulu-Natal | 29.872 | 29.006 | 2 | No |
| False Bay | KwaZulu-Natal | 32.397 | 27.968 | 5H | No |
| Fauresmith | Free State | 25.315 | 29.748 | 1 | No |
| Ficksburg | Free State | 27.880 | 28.876 | 2 | No |
| Fort Beaufort | Eastern Cape | 26.627 | 32.780 | 4 | No |
| Fouriesburg | Free State | 28.209 | 28.621 | 6 | No |
| Frankfort | Free State | 28.493 | 27.277 | 2 | No |
| Fraserburg | Northern Cape | 21.513 | 31.016 | 7 | No |
© SABS 45
SANS 10400-XA:2021 Edition 2
| Table C.1 (continu | ued) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Gamtoos | Eastern Cape | 25.028 | 33.961 | 4 | Yes |
| Gariep | Northern Cape | 16.454 | 28.627 | 4 | No |
| Garies | Northern Cape | 17.990 | 30.565 | 1 | No |
| Gatyana | Eastern Cape | 28.250 | 32.401 | 5 | No |
| Gcuwa | Eastern Cape | 28.150 | 32.331 | 4 | No |
| George | Western Cape | 22.458 | 33.951 | 4 | Yes |
| Germiston | Gauteng | 28.158 | 26.209 | 1 | No |
| Gingindlovu | KwaZulu-Natal | 31.586 | 29.031 | 5H | No |
| Glencoe | KwaZulu-Natal | 30.153 | 28.179 | 5 | No |
| Gourits | Western Cape | 21.880 | 34.337 | 4 | Yes |
| Graaff-Reinet | Eastern Cape | 24.535 | 32.251 | 1 | No |
| Grahamstown | Eastern Cape | 26.525 | 33.307 | 4 | No |
| Graskop | Mpumalanga | 30.840 | 24.934 | 5 | No |
| Greytown | KwaZulu-Natal | 30.588 | 29.064 | 4 | No |
| Griekwastad | Northern Cape | 23.249 | 28.848 | 1 | No |
| Groblersdal | Limpopo | 29.396 | 25.168 | 5 | No |
| Grootdrink | Northern Cape | 22.279 | 26.495 | 5 | No |
| Groot-Kei | Eastern Cape | 28.384 | 32.680 | 5 | No |
| Grootvloer | Northern Cape | 20.750 | 31.146 | 1 | No |
| Hanover | Northern Cape | 24.444 | 31.072 | 1 | No |
| Harding | KwaZulu-Natal | 29.882 | 30.572 | 5H | No |
| Harrismith | Free State | 29.126 | 28.271 | 2 | No |
| Hartbees | Northern Cape | 20.526 | 28.759 | 3 | No |
46 © SABS
SANS 10400-XA:2021
Edition 2
| Table C.1 (continu | ued) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Hartswater | Northern Cape | 24.810 | 27.754 | 1 | No |
| Hebertsdale | Western Cape | 21.763 | 34.015 | 4 | Yes |
| Heidelberg | Gauteng | 28.356 | 26.499 | 2 | No |
| Heidelberg | Western Cape | 20.956 | 34.089 | 4 | No |
| Heilbron | Free State | 27.973 | 27.294 | 2 | No |
| Hennenman | Free State | 27.022 | 27.972 | 1 | No |
| Hermanus | Western Cape | 19.239 | 34.420 | 2 | Yes |
| Hertzogville | Free State | 25.508 | 28.128 | 1 | No |
| Hlobane | KwaZulu-Natal | 30.987 | 27.711 | 4 | No |
| Hluhluwe | KwaZulu-Natal | 32.271 | 28.021 | 5 | No |
| Hondeklipbaai | Northern Cape | 17.277 | 30.318 | 4 | No |
| Hoopstad | Free State | 25.910 | 27.833 | 1 | No |
| Hopefield | Western Cape | 18.349 | 33.058 | 4 | No |
| Hopetown | Northern Cape | 24.087 | 29.624 | 1 | No |
| Hotazel | Northern Cape | 22.962 | 27.203 | 5 | No |
| Houtkraal | Northern Cape | 24.094 | 30.393 | 1 | No |
| Idutywa | Eastern Cape | 28.305 | 32.099 | 4 | No |
| Ingwavuma | KwaZulu-Natal | 31.996 | 27.133 | 5 | No |
| Ixopo | KwaZulu-Natal | 30.061 | 30.153 | 5H | No |
| Jagersfontein | Free State | 25.424 | 29.761 | 1 | No |
| Jamestown | Eastern Cape | 26.804 | 31.131 | 6 | No |
| Johannesburg | Gauteng | 28.039 | 26.202 | 1 | No |
| Kakamas | Northern Cape | 20.616 | 28.768 | 3 | No |
| Kamieskroon | Northern Cape | 17.931 | 30.212 | 1 | No |
| Kareeberge | Northern Cape | 21.165 | 30.714 | 1 | No |
© SABS 47
SANS 10400-XA:2021 Edition 2
| Table C.1 (continu | ued) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Keimoes | Northern Cape | 20.980 | 28.722 | 5 | No |
| Kendrew | Eastern Cape | 24.486 | 32.493 | 5 | No |
| Kenhardt | Northern Cape | 21.152 | 29.348 | 5 | No |
| Kestell | Free State | 28.702 | 28.307 | 1 | No |
| Kimberley | Northern Cape | 24.761 | 28.741 | 1 | No |
| King William's Town |
Eastern Cape | 27.375 | 32.879 | 4 | No |
| Kirkwood | Eastern Cape | 25.446 | 33.401 | 5 | No |
| Klawer | Western Cape | 18.626 | 31.779 | 5 | No |
| Klerksdorp | North West | 26.665 | 26.867 | 1 | No |
| Klipdale | Western Cape | 19.966 | 34.306 | 4 | Yes |
| Klipplaat | Eastern Cape | 24.390 | 33.016 | 5 | No |
| Knysna | Western Cape | 23.050 | 34.035 | 4 | No |
| Koffiefontein | Free State | 25.003 | 29.407 | 1 | No |
| Kokstad | KwaZulu-Natal | 29.418 | 30.539 | 2 | No |
| Komatipoort | Mpumalanga | 31.950 | 25.430 | 3 | No |
| Kompasberg | Eastern Cape | 24.541 | 31.765 | 6 | No |
| Komsberg | Northern Cape | 20.780 | 32.692 | 6 | No |
| Koppies | Free State | 27.573 | 27.242 | 1 | No |
| Koster | North West | 26.898 | 25.869 | 1 | No |
| Kraai | Eastern Cape | 24.013 | 32.484 | 1 | No |
| Kranskop | KwaZulu-Natal | 30.862 | 28.967 | 5H | No |
| Krugersdorp | Gauteng | 27.771 | 26.103 | 1 | No |
| Kruisfontein | Eastern Cape | 24.739 | 34.007 | 4 | No |
| Kuruman | Northern Cape | 23.357 | 27.433 | 1 | No |
| Kwabhaca | Eastern Cape | 28.994 | 30.901 | 2 | No |
48 © SABS
SANS 10400-XA:2021
Edition 2
| Table C.1 (continu | ued) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Kwadukuza | KwaZulu-Natal | 31.289 | 29.328 | 5H | No |
| KwaMashu | KwaZulu-Natal | 30.962 | 29.751 | 5H | No |
| Kwa-Nobuhle | Eastern Cape | 25.388 | 33.818 | 4 | No |
| Ladismith | Western Cape | 21.268 | 33.498 | 2 | No |
| Lady Grey | Eastern Cape | 27.216 | 30.711 | 6 | No |
| Ladysmith | KwaZulu-Natal | 29.782 | 28.559 | 5 | No |
| Laingsburg | Western Cape | 20.854 | 33.193 | 2 | No |
| Lambert's Bay | Western Cape | 18.305 | 32.095 | 5 | No |
| Langebaan | Western Cape | 8.037 | 33.081 | 4 | No |
| Langeberg | Western Cape | 20.130 | 33.782 | 2 | No |
| Langklip | Northern Cape | 20.329 | 28.213 | 3 | No |
| Leeu Gamka | Western Cape | 21.977 | 32.777 | 1 | No |
| Lepalale | Limpopo | 27.717 | 23.687 | 3 | No |
| Letaba | Limpopo | 30.067 | 23.900 | 5 | No |
| Letjiesbos | Western Cape | 22.271 | 32.563 | 1 | No |
| Libode | Eastern Cape | 22.248 | 32.553 | 4 | No |
| Lichtenburg | North West | 26.160 | 26.151 | 1 | No |
| Loeriesfontein | Northern Cape | 19.445 | 30.953 | 1 | No |
| Loskop Dam | Mpumalanga | 29.329 | 25.429 | 5 | No |
| Lothair | Mpumalanga | 30.438 | 26.391 | 2 | No |
| Louis Trichardt | Limpopo | 29.904 | 23.046 | 5 | No |
| Louwsburg | KwaZulu-Natal | 21.283 | 27.576 | 5 | No |
| Loxton | Northern Cape | 19.405 | 30.941 | 1 | No |
© SABS 49
SANS 10400-XA:2021 Edition 2
| Table C.1 (continue | ed) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Luckhoff | Free State | 24.787 | 29.748 | 1 | No |
| Lutzputs | Northern Cape | 20.666 | 28.387 | 3 | No |
| Luvuvhu | Limpopo | 31.268 | 22.402 | 3 | No |
| Maclear | Eastern Cape | 28.350 | 31.070 | 2 | No |
| Madadeni | KwaZulu-Natal | 30.072 | 27.752 | 2 | No |
| Mahikeng | North West | 25.632 | 25.857 | 5 | No |
| Magaliesburg | Gauteng | 27.542 | 25.989 | 1 | No |
| Makwassie | North West | 25.996 | 27.319 | 1 | No |
| Malmesbury | Western Cape | 18.724 | 33.463 | 1 | Yes |
| Mangaung | Free State | 26.496 | 29.322 | 1 | No |
| Maretsane | North West | 25.421 | 26.142 | 5 | No |
| Margate | KwaZulu-Natal | 30.376 | 30.854 | 5H | No |
| Marquard | Free State | 27.428 | 28.665 | 2 | No |
| Matatiele | Eastern Cape | 28.815 | 30.346 | 6 | No |
| Matjiesfontein | Western Cape | 20.580 | 33.228 | 2 | No |
| Matroosberg | Western Cape | 19.655 | 33.374 | 6 | No |
| Maxesibenj | Eastern Cape | 28.830 | 30.855 | 2 | No |
| Mbashe | Eastern Cape | 28.327 | 31.728 | 2 | No |
| Mdantsane | Eastern Cape | 27.709 | 32.968 | 5 | No |
| Memel | Free State | 29.568 | 27.681 | 2 | No |
| Middelburg | Eastern Cape | 25.006 | 31.493 | 2 | No |
| Middelburg | Mpumalanga | 29.456 | 25.763 | 2 | No |
| Middelwit | North West | 27.036 | 24.852 | 5 | No |
50 © SABS
SANS 10400-XA:2021
Edition 2
| Table C.1 (contin | nued) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Mkomazi | KwaZulu-Natal | 29.472 | 29.633 | 2 | No |
| Mkuze | KwaZulu-Natal | 32.038 | 27.617 | 5 | No |
| Mmabatho | North West | 25.615 | 25.834 | 5 | No |
| Modderrivier | Northern Cape | 24.638 | 29.022 | 1 | No |
| Modimolle | Limpopo | 28.404 | 24.701 | 5 | No |
| Mogalakwena | Limpopo | 29.011 | 24.193 | 5 | No |
| Molteno | Eastern Cape | 26.351 | 31.393 | 6 | No |
| Mbombela | Mpumalanga | 30.962 | 25.469 | 5 | No |
| Mooi River | KwaZulu-Natal | 29.997 | 29.207 | 2 | No |
| Moorreesburg | Western Cape | 18.664 | 33.138 | 5 | Yes |
| Mopane | Limpopo | 29.852 | 22.623 | 3 | No |
| Morgenzon | Mpumalanga | 29.617 | 26.731 | 2 | No |
| Mosselbaai | Western Cape | 22.110 | 34.129 | 4 | Yes |
| Mount Fletcher | Eastern Cape | 28.504 | 30.690 | 6 | No |
| Mqanduli | Eastern Cape | 28.762 | 31.819 | 5 | No |
| Mtubatuba | KwaZulu-Natal | 32.185 | 28.416 | 5H | No |
| Mtwalume | KwaZulu-Natal | 30.630 | 30.491 | 5H | No |
| Murraysburg | Western Cape | 23.766 | 31.967 | 1 | No |
| Musina | Limpopo | 30.037 | 22.330 | 3 | No |
| Mzimvubu | KwaZulu-Natal | 29.544 | 31.615 | 5H | No |
| Nababeep | Northern Cape | 17.784 | 29.589 | 1 | No |
| Nelspoort | Western Cape | 23.003 | 32.116 | 1 | No |
| New Hanover | KwaZulu-Natal | 30.527 | 29.354 | 4 | No |
© SABS 51
SANS 10400-XA:2021 Edition 2
| Table C.1 (continue | ed) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Newcastle | KwaZulu-Natal | 29.926 | 27.755 | 2 | No |
| Niekerkshoop | Northern Cape | 22.837 | 29.327 | 1 | No |
| Nieuwoudtville | Northern Cape | 19.100 | 31.372 | 5 | No |
| Nigel | Gauteng | 28.471 | 26.423 | 2 | No |
| Nkandla | KwaZulu-Natal | 31.057 | 28.586 | 5 | No |
| Nongoma | KwaZulu-Natal | 31.634 | 27.896 | 5 | No |
| Northam | Limpopo | 27.263 | 24.953 | 5 | No |
| Noupoort | Northern Cape | 24.952 | 31.178 | 2 | No |
| Nqutu | KwaZulu-Natal | 30.681 | 28.206 | 4 | No |
| Nuwerus | Western Cape | 18.357 | 31.149 | 5 | No |
| Odendaalsrus | Free State | 26.701 | 27.880 | 1 | No |
| Okiep | Northern Cape | 17.874 | 29.594 | 1 | No |
| Olifantshoek | Northern Cape | 22.737 | 27.941 | 1 | No |
| Orkney | North West | 26.689 | 27.008 | 1 | No |
| Osizweni | KwaZulu-Natal | 30.119 | 27.786 | 2 | No |
| Ottosdal | North West | 26.006 | 26.812 | 1 | No |
| Paarl | Western Cape | 18.970 | 33.764 | 2 | Yes |
| Pakhuis | Western Cape | 18.989 | 32.139 | 5 | No |
| Pampoenpoort | Northern Cape | 22.657 | 31.061 | 1 | No |
| Park Rynie | KwaZulu-Natal | 30.737 | 30.317 | 5H | No |
| Parys | Free State | 27.460 | 26.898 | 1 | No |
| Patensie | Eastern Cape | 24.813 | 33.758 | 4 | No |
| Paulpietersburg | KwaZulu-Natal | 30.819 | 27.428 | 4 | No |
52 © SABS
SANS 10400-XA:2021
Edition 2
| Table C.1 (continu | ued) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Peddie | Eastern Cape | 27.119 | 33.198 | 5 | No |
| Pella | Northern Cape | 19.155 | 29.034 | 5 | No |
| Pepani | North West | 23.780 | 26.251 | 5 | No |
| Petrus Steyn | Free State | 28.129 | 27.649 | 2 | No |
| Petrusburg | Free State | 25.414 | 29.115 | 1 | No |
| Philippolis | Free State | 25.274 | 30.266 | 1 | No |
| Philipstown | Northern Cape | 24.473 | 30.437 | 1 | No |
| Pienaarsrivier | Limpopo | 28.295 | 25.208 | 5 | No |
| Piet Retief | Mpumalanga | 30.808 | 27.005 | 4 | No |
| Pietermaritzburg | KwaZulu-Natal | 30.377 | 29.601 | 4 | No |
| Piketberg | Western Cape | 18.757 | 32.908 | 5 | No |
| Pilgrim's Rest | Mpumalanga | 30.756 | 24.907 | 1 | No |
| Pinetown | KwaZulu-Natal | 30.861 | 29.813 | 5H | No |
| Pofadder | Northern Cape | 19.392 | 29.125 | 5 | No |
| Polokwane | Limpopo | 29.453 | 23.909 | 5 | No |
| Port Alfred | Eastern Cape | 26.893 | 33.588 | 5 | Yes |
| Port Elizabeth | Eastern Cape | 25.622 | 33.962 | 4 | Yes |
| Port Nolloth | Northern Cape | 16.882 | 29.257 | 4 | No |
| Port Shepstone | KwaZulu-Natal | 30.453 | 30.739 | 5H | No |
| Port St Johns | Eastern Cape | 29.543 | 31.621 | 5H | No |
| Porterville | Western Cape | 18.993 | 33.015 | 1 | Yes |
| Postmasburg | Northern Cape | 23.063 | 28.331 | 1 | No |
| Potchefstroom | North West | 27.096 | 26.719 | 1 | No |
© SABS 53
SANS 10400-XA:2021 Edition 2
| Table C.1 (contin | nued) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Pretoria | Gauteng | 28.190 | 25.744 | 5 | No |
| Prieska | Northern Cape | 22.747 | 29.666 | 1 | No |
| Prince Albert | Western Cape | 22.027 | 33.214 | 2 | No |
| Punda Maria | Limpopo | 31.016 | 22.691 | 3 | No |
| Queenstown | Eastern Cape | 26.868 | 31.895 | 2 | No |
| Qumbu | Eastern Cape | 28.869 | 31.160 | 2 | No |
| Quoin Point | Western Cape | 19.638 | 34.781 | 4 | Yes |
| Randfontein | Gauteng | 27.706 | 26.173 | 1 | No |
| Reddersburg | Free State | 26.178 | 29.651 | 1 | No |
| Reitz | Free State | 28.428 | 27.801 | 2 | No |
| Reivilo | North West | 24.182 | 27.565 | 1 | No |
| Richards Bay | KwaZulu-Natal | 32.053 | 28.750 | 5H | No |
| Riebeek -Oos | Eastern Cape | 26.149 | 33.202 | 5 | No |
| Riversdale | Western Cape | 21.255 | 34.042 | 4 | Yes |
| Robertson | Western Cape | 19.888 | 33.799 | 2 | Yes |
| Roodepoort | Gauteng | 27.869 | 26.160 | 1 | No |
| Rosmead | Eastern Cape | 25.119 | 31.491 | 2 | No |
| Rouxville | Free State | 26.835 | 30.416 | 2 | No |
| Rustenburg | North West | 27.278 | 25.635 | 5 | No |
| Sakrivier | Northern Cape | 20.438 | 30.882 | 1 | No |
| Saldanha Bay | Western Cape | 17.943 | 33.007 | 4 | No |
| Sannaspos | Free State | 26.548 | 29.160 | 1 | No |
54 © SABS
SANS 10400-XA:2021
Edition 2
| Table C.1 (continu | ued) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Sannieshof | North West | 25.808 | 26.531 | 1 | No |
| Seekoei | Northern Cape | 25.016 | 30.308 | 1 | No |
| Senekal | Free State | 27.618 | 28.321 | 2 | No |
| Settlers | Limpopo | 28.542 | 24.957 | 5 | No |
| Simonstown | Western Cape | 18.435 | 34.193 | 4 | Yes |
| Sishen | Northern Cape | 22.983 | 27.783 | 5 | No |
| Smithfield | Free State | 26.530 | 30.212 | 1 | No |
| Soekmekaar | Limpopo | 29.928 | 24.493 | 5 | No |
| Springbok | Northern Cape | 17.886 | 29.665 | 1 | No |
| Springs | Gauteng | 28.441 | 26.256 | 2 | No |
| Standerton | Mpumalanga | 29.226 | 26.954 | 2 | No |
| Stellenbosch | Western Cape | 18.866 | 33.931 | 2 | Yes |
| Tarkastad | Eastern Cape | 26.260 | 32.006 | 2 | No |
| Theunissen | Free State | 26.714 | 28.400 | 1 | No |
| Thohoyandou | Limpopo | 30.458 | 22.977 | 3 | No |
| Tom Burke | Limpopo | 27.988 | 23.070 | 3 | No |
| Tongaat | KwaZulu-Natal | 31.141 | 29.543 | 5H | No |
| Touws | Western Cape | 21.153 | 33.790 | 2 | Yes |
| Tsineng | Northern Cape | 23.078 | 27.088 | 5 | No |
| Tsolo | Eastern Cape | 28.753 | 31.309 | 2 | No |
| Tulbagh | Western Cape | 19.141 | 33.284 | 1 | Yes |
| Tzaneen | Limpopo | 30.169 | 23.821 | 5 | No |
© SABS 55
SANS 10400-XA:2021 Edition 2
| Table C.1 (continu | ued) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Ubombo | KwaZulu-Natal | 32.083 | 27.563 | 5 | No |
| Ugie | Eastern Cape | 28.236 | 31.194 | 2 | No |
| Uitenhage | Eastern Cape | 25.397 | 33.757 | 4 | Yes |
| Ulco | Northern Cape | 24.220 | 28.335 | 1 | No |
| Umkomaas | KwaZulu-Natal | 30.796 | 30.207 | 5H | No |
| Umtata | Eastern Cape | 28.789 | 31.592 | 4 | No |
| Umzimvubu | Eastern Cape | 28.993 | 30.902 | 2 | No |
| Uniondale | Western Cape | 23.123 | 33.659 | 2 | No |
| Upington | Northern Cape | 21.217 | 28.459 | 5 | No |
| Utrecht | KwaZulu-Natal | 30.322 | 27.656 | 2 | No |
| Vaalwater | Limpopo | 28.111 | 24.299 | 5 | No |
| Vanderbijlpark | Gauteng | 27.839 | 26.697 | 1 | No |
| Vanrhynsdorp | Western Cape | 18.743 | 31.609 | 5 | No |
| Vanwyksvlei | Northern Cape | 21.825 | 30.366 | 1 | No |
| Ventersburg | Free State | 27.136 | 28.086 | 1 | No |
| Venterstad | Eastern Cape | 25.799 | 30.778 | 1 | No |
| Vereeninging | Gauteng | 27.928 | 26.675 | 1 | No |
| Verneukpan | Northern Cape | 21.067 | 30.133 | 1 | No |
| Victoria West | Northern Cape | 23.121 | 31.404 | 1 | No |
| Villiers | Free State | 28.599 | 27.028 | 2 | No |
| Virginia | Free State | 26.874 | 28.098 | 1 | No |
| Volksrust | Mpumalanga | 29.886 | 27.367 | 2 | No |
56 © SABS
SANS 10400-XA:2021
Edition 2
| Table C.1 (continue | ed) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Vredefort | Free State | 27.365 | 27.006 | 1 | No |
| Vredenburg | Western Cape | 17.987 | 32.906 | 4 | No |
| Vrendendal | Western Cape | 18.505 | 31.664 | 5 | No |
| Vryburg | North West | 24.731 | 26.955 | 1 | No |
| Vryheid | KwaZulu-Natal | 30.795 | 27.767 | 4 | No |
| Wakkerstroom | Mpumalanga | 30.149 | 27.349 | 2 | No |
| Warden | Free State | 28.965 | 27.854 | 2 | No |
| Warrenton | Northern Cape | 24.845 | 28.109 | 1 | No |
| Wasbank | KwaZulu-Natal | 30.103 | 28.314 | 5 | No |
| Waterberge | Limpopo | 28.311 | 24.331 | 5 | No |
| Waterval-Boven | Mpumalanga | 30.328 | 25.643 | 2 | No |
| Waterval-Onder | Mpumalanga | 30.383 | 25.648 | 2 | No |
| Weenen | KwaZulu-Natal | 30.084 | 28.851 | 2 | No |
| Welkom | Free State | 26.732 | 27.978 | 1 | No |
| Wepener | Free State | 27.039 | 29.729 | 2 | No |
| Wilge | Mpumalanga | 28.987 | 25.976 | 2 | No |
| Wiliston | Northern Cape | 20.919 | 31.340 | 1 | No |
| Willowmore | Eastern Cape | 23.487 | 33.295 | 2 | No |
| Windsorton | Northern Cape | 24.713 | 28.331 | 1 | No |
| Wolmaransstad | North West | 25.985 | 27.200 | 1 | No |
| Wolseley | Western Cape | 19.198 | 33.414 | 2 | Yes |
| Worcester | Western Cape | 19.444 | 33.646 | 2 | No |
© SABS 57
SANS 10400-XA:2021 Edition 2
| Table C.1 (concl | luded) | Col3 | Col4 | Col5 | Col6 |
|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | 5 | 6 |
| City/Town | Province | Longitude (°E) | Latitude (°S) | Energy zone | SCCP |
| Xora | Eastern Cape | 28.656 | 31.953 | 5 | No |
| Zebediela | Limpopo | 29.249 | 24.301 | 5 | No |
| Zeerust | North West | 26.086 | 25.544 | 5 | No |
58 © SABS
SANS 10400-XA:2021
Edition 2
Annex D
(informative)
Types of shading devices
The types of shading devices that may comply are not limited to the examples in figure D.1.
Figure D.1 — Shading devices
© SABS 59
SANS 10400-XA:2021 Edition 2
Annex E
(informative)
Whole glazing element performance values
Table E.1 provides ranges of whole glazing element performance values to be used in conjunction with table 4 to specify fenestration.
Table E.1 — Indicative ranges of whole glazing element performance values
| 1 | Col2 | 2 | 3 | Col5 | Col6 | Col7 |
|---|---|---|---|---|---|---|
Glass description |
Glass description |
Comment | Performance values | Performance values | Performance values | Performance values |
Glass description |
Glass description |
Comment | Total U-value range (W/m².K |
Total U-value range (W/m².K |
SHGC range | SHGC range |
Glass description |
Glass description |
Comment | Metal framing |
Timber/ Thermal break/ uPVC framing |
Metal framing |
Timber/ Thermal break/ uPVC framing |
Single - (monolithic or laminated) |
Clear | Minimal variation in glass U-value and SHGC for difference glass thicknesses. |
7,9 to 5,5 | 5,6 to 4,3 | 0,81 to 0,64 | 0,77 to 0,51 |
Single - (monolithic or laminated) |
Tinted | Glass SHGC depends on glass thickness and type of tint. |
7,9 to 5,6 | 5,6 to 4,3 | 0,65 to 0,33 | 0,61 to 0,25 |
Single - (monolithic or laminated) |
Coated | Glass U-value and SHGC depend on coating type. |
7,8 to 3,8 | 5,5 to 2,9 | 0,68 to 0,36 | 0,64 to 0,27 |
Single - (monolithic or laminated) |
Tinted and coated |
Glass U-value depends on coating type. Glass SHGC depends on coating type, type of tint and glass thickness. |
7,8 to 3,8 | 5,5 to 3,1 | 0,45 to 0,31 | 0,42 to 0,23 |
Double |
Clear | Glass U-value depends on cavity width. |
6,2 to 3,1 | 3,8 to 2,5 | 0,72 to 0,63 | 0,68 to 0,47 |
Double |
Tinted | Glass U-value depends on cavity width. Glass SHGC depends on type of tint, tinted glass thickness and on cavity width. |
6,2 to 3,1 | 3,8 to 2,5 | 0,57 to 0,36 | 0,57 to 0,27 |
Double |
Coated | Glass U-value depends on cavity width and type of coating. Glass SHGC depends on type of coating and cavity width. |
6,1 to 2,4 | 3,8 to 2,1 | 0,60 to 0,22 | 0,59 to 0,17 |
Double |
Tinted and coated |
Glass U-value depends on cavity width and type of coating. Glass SHGC depends on type of coating, tinted glass thickness and cavity width. |
6,1 to 2,5 | 3,8 to 2,1 | 0,41 to 0,21 | 0,37 to 0,16 |
60 © SABS
SANS 10400-XA:2021
Edition 2
Annex F
(informative)
The installation of insulation in roof assemblies F.1 Some insulation products may not have been tested in accordance with SANS 8301 and stated
insulation levels on some manufacturer’s literature may not be achievable as it is the declared value and does not take aspects such as thermal bridging, compression etc. into account. The performance of the insulation used should be validated by test reports.
F.2 When installed in a building, insulation should form a consistent and continuous barrier (see
5.6.1(b)). This is important as any gaps within the barrier will allow heat in or out, which will undermine the effectiveness of the overall energy efficiency measures. However, certain gaps are essential especially adjoining services and light fittings where the proximity of insulation may create a fire hazard.
F.3 Heat can bypass insulation by travelling along metal framing systems. For this reason, a thermal
break (spacer) in roofing systems where a metal frame member connects the outer cladding or roofing with the inner lining (insulation) should be provided (see 5.6.3). Without this thermal break the insulation's effectiveness can be reduced by as much as a half thereby requiring more insulation to achieve the same total R-Value.
F.4 The requirements for reflective insulation are given in 5.6.4. Insulating performance is achieved
by the ability of the reflective insulation to "reflect" heat at one surface and not transmit it at another, combined with the insulating qualities of the thin air films adjacent to the reflective insulation. Some reflective insulation is also bonded to bulk or board insulation providing enhanced performance. Accordingly, the reflectivity value and the presence of an airspace are critical, because without this airspace the reflection will not occur. Generally reflective insulation has a dull or anti-glare (painted side) and a shiny silver side. Both sides will achieve a degree of reflectivity. However, the shiny side is the most effective. Overlapping of reflective insulation should not be less than specified by the installation specifications.
F.5 The requirements for bulk insulation are given in 5.6.6. The term bulk insulation includes glass
fibre, cellulose fibre, polyester, polyisocyanurate and polystyrene. These materials tend to have a high percentage of air voids that retard heat movement. The thermal performance of bulk insulation is dependent on the material retaining the thickness specified by the manufacturer, in accordance with the required test results. The thickness of the insulation is critical because the air pockets within the material trap and retard heat flow. If the insulation is compressed it will lose some of these air pockets as the fibre contact increases, which in turn will reduce its capacity to achieve the design Rvalue.
F.6 Typical details of insulation installation are given in figures F.1, F.2, F.3, F.4 and F.5.
© SABS 61
SANS 10400-XA:2021 Edition 2
Figure F.1 — Rigid board insulation installed over purlin
Figure F.2 — Bulk Insulation installed over purlin with mechanical spacer
Figure F.3 — Bulk insulation installed over purlin with continuous solid spacer
62 © SABS
SANS 10400-XA:2021
Edition 2
Figure F.4 — Tiled roof with reflective foil insulation installed over rafters with 38 mm airgap (brandering) and rigid bulk insulation
installed on top of ceiling
Figure F.5 — Tiled roof with reflective foil insulation installed over rafters with 38 mm airgap (brandering) and rigid bulk insulation fixed
to underside of the rafters
© SABS 63
SANS 10400-XA:2021 Edition 2
Bibliography
SANS 10400-A, The application of the National Building Regulations – Part A – General principles and requirements.
64 © SABS
Fencalc XA2021